Lennox INNOV DM R Series Application Manual page 95

Close control unit ec plug fan
Table of Contents

Advertisement

8
Operating Parameters Setting
8.1
Generalities
All the control devices are set and tested in the factory before the unit is dispatched. However, after the unit has
been in service for a reasonable period of time you can perform a check on the operating and safety devices.
The settings are shown in Tab. 6 and Tab. 7.
All servicing of the equipment is to be considered extraordinary maintenance and may be
carried out BY QUALIFIED TECHNICIANS ONLY: incorrect settings may cause serious damage
to the unit and injuries to persons.
The operating parameters and control system settings configurable by means of the microprocessor control are
password protected if they have a potential impact on the integrity of the unit.
Tab. 6
Setting of control devices
Differential air pressure switch (outlet air flow)
Differential air pressure switch (dirty filter)
Values to be calibrated depending on the application.
Tab. 7
Setting of safety-control devices
Maximum pressure switch
Minimum pressure switch
Modulating condensation control device
Time lapse between two compressor starts
8.2
Maximum pressure switch
The high pressure switch stops the compressor when the outlet pressure exceeds the set value.
Warning:
latter
open.
The high pressure switch must be manually reset; this is possible only when the pressure falls below the set
differential (see Tab. 7).
8.3
Minimum pressure switch
The low pressure switch stops the compressor when the inlet pressure falls below the set value for more than
180 seconds. The switch is automatically reset when the pressure rises above the set differential (see Tab. 7).
INNOV@ CENT -AGU-0912-E
Control device
Control device
Do not attempt to change the setting of the maximum pressure switch: Should the
fail to trip in the event of a pressure increase, the pressure relief valve will
Set point
Pa
50
Pa
50
Activation
Bar
28.0
Bar
2.0
Bar
14.0
s
480
Differential
30
20
Differential
Resetting
4.0
Manual
1.5
Automatic
7.0
-
-
-
. 19 .