Lennox INNOV DM R Series Application Manual page 81

Close control unit ec plug fan
Table of Contents

Advertisement

1.2
Field of application
All INNOV@ units are to be used within the operating limits stated in this manual; failure to comply with said
limits will invalidate the warranties provided in the contract of sale (see Tab. 1, Tab. 2 and Fig. 3).
Tab. 1
Operating limits "DX version"
Power supply limits and storage conditions for "DX" version
Model
Power supply
Storage conditions
Tab. 2
Operating limits "CW version"
Power supply limits and storage conditions for "CW" version
Model
Power supply
Storage conditions
Fig. 3
Application limits
F
DMA . . . C
i
Air condensed versions
g
.
R.H. £ 65%
°C
3
32
28
18
20
Condenser air temperature
1.3
Cooling circuit (DX version)
The entire refrigerating circuit is assembled in our warehouse including all pipe work and using only primary
brand for components. The workers involved in the welding and pipe work process are qualified by a third part
according CEE 97/23 PED directive: it is worth to be underlined that this qualification for workers were not
request, but it is our own decision taking care of the quality and/or in general to the customer satisfaction. All DX
unit ("A", "W", "F", "D", "Q" versions) are in single circuit execution and are prechargerd with dry nitrogen for
"A", "D" or with R407C refrigerant for "W", "F", "Q" versions.
Refrigerant different from R407C, like R22, R134a, R410A are available on request and previous check for local
rules.
Compressors
On INNOV@ units are installed only primary brand scroll compressors. Scroll compressor represent for CCAC
units the best solution in terms of efficiency and reliability. The internal compression ratio is very close to the
typical operating condition of CCAC giving the maximum in terms of COPs and the perfect balanced pressures at
start up gives big advantages to the e-motor in terms of reliability, mainly in this filed where frequent start up may
be
All motors are thermally protected with an internal sensors chain: in case of overload this sensor opens without
giving contacts to the connection box.
Cooling components
INNOV@ CENT -AGU-0912-E
DMA . . . C
230 Vac ±10 %
-10 °C / 90 % R.H.
+55 °C / 90 % R.H.
DMC . . . C
230 Vac ±10 %
-10 °C / 90 % R.H.
+60 °C / 90 % R.H.
DMW . . . C
Water condensed versions
°C
32
28
18
40 45
25
°C
Condenser water temperature
R.H. £ 65%
40 43
°C
DMC . . . C
Chilled water versions
R.H. £ 65%
°C
32
27
20
5
7
Chilled water temperature
possible.
. 5 .
16
°C