Lennox INNOV DM R Series Application Manual page 98

Close control unit ec plug fan
Table of Contents

Advertisement

9.3
Repairing the cooling circuit
Warning:
compressors,
Even if briefly exposed to
large amounts of humidity, which results in the formation of
weak acids.
If the cooling circuit has undergone any repairs, the following operations must be carried out:
D tightness test;
D evacuation and drying of the cooling circuit;
D charging with refrigerant.
If the system has to be drained, always recover the refrigerant present in the circuit using
suitable equipment; the refrigerant should be handled exclusively in the liquid phase.
9.4
Tightness test
Fill the circuit with anhydrous nitrogen supplied from a tank with a pressure-reducing valve until the pressure
rises to 22 bars.
During the pressurisation phase, do not exceed a pressure of 22 bars on the compressor low
pressure side.
The presence of any leaks must be determined using special leak detectors. Should any leaks be detected
during the test, empty out the circuit before repairing the leaks with suitable alloys.
Do not use oxygen in the place of nitrogen as a test agent, since this would cause a risk of
explosion.
9.5
Hard vacuum and drying of cooling circuit
To achieve a hard vacuum in the cooling circuit it is necessary to use a pump capable of generating a high
degree of vacuum, i.e. 150 Pa of absolute pressure with a capacity of approximately 10 m
available,
one
evacuation
If there is no such vacuum pump available, or whenever the circuit has remained open for long periods of time,
you are strongly recommended to adopt the triple evacuation method. This method is also recommended when
there is a presence of humidity within the circuit. The vacuum pump should be connected to the inlets.
The procedure to be carried out is as follows:
D Evacuate the circuit until you reach an absolute pressure of at least 350 Pa: at this point inject nitrogen into
the circuit until you reach a relative pressure of about 1 bar.
D Repeat the step described above.
D Carry out the step described above for the third time, but in this case attempting to reach the hardest vacuum
possible.
Using this procedure you can easily remove up to 99% of pollutants.
INNOV@ CENT -AGU-0912-E
While performing repairs on the cooling circuit or maintenance work on the
make sure the circuit is left open for as little time as possible.
will
normally
suffice
air, ester oils tend to absorb
to
achieve
an
absolute
3
/h. If such a pump is
pressure
of
150
Pa.
. 22 .

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Innov dma r seriesInnov dmc r series

Table of Contents