Fancoil controller

Advertisement

Page 10 / 15
PI controller
Address
277
0x0115
278
0x0116
279
0x0117
280
0x0118
281
0x0119
283
0x011B
284
0x011C
285
0x011D
286
0x011E
287
0x011F
288
0x0120
289
0x0121
290
0x0122
291
0x0123
296
0x0128
297
0x0129
298
0x012A
299
0x012B
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Deutschland · tel: 02778/6960-0 · fax: -400 ·
Access
Description
Read-only
Controller mode Comfort :
0b0000 0000=controller off
0b0000 0001=controller auto mode
0b0000 0010=controller heating mode only
0b0000 0011=controller cooling mode only
0b0000 0100=ventilating
only, valves closed)
Controller mode ECO:
0b0001 0000=controller off
0b0001 0001=controller auto mode
0b0001 0010=controller heating mode only
0b0001 0011=controller cooling mode only
0b0001 0100=ventilating
only, valves closed)
HMI mode
0b1xxx xxxx = HMI Mode, controller OFF
0b1xxx xx01 = show symbol "ventilating"
0b1xxx xx10 = show symbol "heating"
0b1xxx xx11 = show symbol "cooling"
0b1xxx x1xx = show symbol " AUTO mode"
0b1xxx x110 = show "AUTO + heating" symbol
0b1xxx x111 = show "AUTO + cooling" symbol
0b1xxx x101 = show "AUTO + ventilating" symbol
0b1xxx 1xxx = reserved
Fan coil type
Read-write
0b00000000= 2-pipe:cooling&heating with Change-
Over
0b00000001= 4-pipe:cooling&heating / (or if 6WV
used)
0b0000001X=electric-heater
Read-write
Fan stages and operation modes
0b00000000 = none,
symbol will not be displayed)
0bxxxx0001 = single stage
0bxxxx0010 = 2 stages
0bxxxx0011 = 3 stages
0bxxxx1000 = EC Fan
0b0001xxxx = fan works not in heating mode
0b0010xxxx = fan works not in cooling/ventilation mode
(0b0011xxxx = fan works not in heating & cooling
mode)
Read-write
Start fan at highest stage for (_) seconds
0...60 = 0..60 seconds
Read-write
Fan OFF-Delay
0= fan never stops
1..255 = Fan stops 1...255 minutes after valves closing
Deadband
Read-write
1...100 = 0,1...10,0 °C/°F
Read-write
Heating Proportional Band Xp_heat
1...100 = 0,1...10,0 °C/°F
Read-write
Heating Integration Time Tn_heat
0...255 = 0...255 Minutes
Read-write
Cooling Proportional Band Xp_cool
1...100 -> 0,1...10,0°C/°F
Cooling Integration Time Tn_cool
Read-write
0...255 = 0...255 Minutes
Minimal limit of the control variable heat
Read-write
0..100
Read-write
Maximal limit of the control variable heat
0..100
Read-write
Minimal limit of the control variable cool
0..100
Maximal limit of the control variable cool
Read-write
0..100
Fan stage 1 (LOW) Voltage value
Read-write
0..100 = 0..10 V
Read-write
Fan stage 2 (Medium) Voltage value
0..100 = 0..10 V
Read-write
Frost protection temperature threshold
50..150 = +5,0..+15,0 °C
Change-Over Temperature Threshold for Heating
Read-write
0..500 = 0..+50,0 °C
LCF02-Touch_3AO2DO_Datasheet_en.docx © 2020
(Frost protection active)
(heating&cooling)
(PI loop controls fan stages
(Frost protection active)
(heating&cooling)
(PI loop controls fan stages
(fan key is locked and the fan
Issue Date: 22.01.2020
Resolution / Unit
1.0
s
1.0
min
0.1
°C/°F
0.1
°C/°F
1.0
min
0.1
°C/°F
1.0
min
1.0
%
1.0
%
1.0
%
1.0
%
0.1
%
0.1
%
0.1
°C/°F
0.1
°C/°F
www.thermokon.de
·
email@thermokon.de
Default
1
1
3
0
15
10
20
30
20
30
0
100
0
100
35
70
70
300