USB to NXS-UPS
If installed with the NXS-UPS modules, connect a USB "A–B type" cable between the SITOP UPS and one of the
USB ports on the NXS (any one). In addition, you must set the DIP switches on the NXS-UPS to specific positions,
for operation with Niagara software. See
Figure 12
USB to NXS-UPS connections.
1 0
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
See
Table 2
for DIP
L+
switch details.
M
L+
Table 2
DIP switch settings on SITOP UPS for use with NXS.
NXS-UPS DIP Switch
Switch
Pos. (0=Off)
1
0
2
0
3
1 (On)
4
0
5
0
6
1 (On)
7
0
8
1 (On)
9
0
10
0
Figure 12
SITOP UPS
L+
In
M
L+
Out
M
B+
Bat
B–
USB A–B type Cable
Default/Recommended Setting
Cut-in threshold is 22.5 volts.
End-of-charge voltage is 27.0 volts.
Charging current is 0.7A.
and
Table
2.
NXS
13
W-NXS AND CP-NXS
74-4059—01