VOLTAGE
RANGE
UNIT
V-PH-HZ
SIZE 702B
MIN MAX
024
208/230–1–60 187
030
208/230–1–60 187
036
208/230–1–60 187
042
208/230–1–60 187
048
208/230–1–60 187
060
208/230–1–60 187
* Heater capacity (kW) based on heater voltage of 208-v & 240-v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. Refer
to Multiplication Factors Table 23.
TABLE 8—702B WITH ICM FIOP ELECTRICAL DATA
OUTDOOR
COMPRESSOR
FAN
MOTOR
RLA
LRA
FLA
253
13.5
61.0
0.9
253
14.7
73.0
0.9
253
15.4
83.0
0.9
253
18.6
105.0
0.9
253
20.5
109.0
1.6
253
27.6
158.0
1.6
INDOOR
ELECTRIC
FAN
HEAT
MOTOR
FLA
Nominal kW*
-/-
3.8/5.0
18.1/20.8
4.3
5.4/7.2
25.9/30.0
7.5/10.0
36.1/41.7
-/-
3.8/5.0
18.1/20.8
4.3
5.4/7.2
25.9/30.0
7.5/10.0
36.1/41.7
-/-
3.8/5.0
18.1/20.8
6.8
5.4/7.2
25.9/30.0
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
-/-
3.8/5.0
18.1/20.8
5.4/7.2
25.9/30.0
6.8
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
15.0/20.0
72.2/83.3
-/-
3.8/5.0
18.1/20.8
5.4/7.2
25.9/30.0
6.8
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
15.0/20.0
72.2/83.3
-/-
3.8/5.0
18.1/20.8
5.4/7.2
25.9/30.0
9.1
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
15.0/20.0
72.2/83.3
—19—
SINGLE POINT
POWER SUPPLY
MAX FUSE
FLA
MCA
OR CKT. BKR.
-/-
22.1/22.1
30/30
27.9/31.4
30/35
37.8/42.9
40/50
50.5/57.5
60/60
-/-
23.5/23.5
30/30
27.9/31.4
30/35
37.8/42.9
40/50
50.5/57.5
60/60
-/-
27.0/27.0
35/35
31.1/34.5
35/40
40.9/46.0
50/50
53.6/60.6
60/–
76.2/86.6
–
-/-
31.0/31.0
40/10
31.1/34.5
40/40
40.9/46.0
50/50
53.6/60.6
60/–
76.2/86.6
–
98.8/112.7
–
-/-
34.0/34.0
40/40
34.0/34.5
40/40
40.9/46.0
50/50
53.6/60.6
60/-
76.2/86.6
–
98.8/112.7
–
-/-
45.2/45.2
60/60
45.2/45.2
60/60
43.8/48.9
50/50
56.5/63.5
60/-
79.1/89.5
–
101.6/115.5
–
MOCP
–
–
–
–
–
–
–
–
–
–
–
–/70
80/90
–
–
–
–/70
90/90
100/125
–
–
–
–/70
90/90
100/125
–
–
–
–/70
90/90
110/125