Bryant 702B Installation, Start-Up, And Operating Instructions Manual page 16

Icm fiop installation instructions
Table of Contents

Advertisement

UNIT SIZE 683B
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
COMPRESSORS
Quantity
REFRIGERANT (R-410A)
Quantity (lb.)
REFRIGERANT METERING DEVICE
Orifice Indoor (in.)
Check-Flo-Rater™ Piston
REFRIGERANT METERING DEVICE
Orifice Outdoor (in.)
Check-Flo-Rater™ Piston
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
OUTDOOR FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
INDOOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor (HP)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Burner Orifice No. (Qty...Drill Size)
Propane Gas
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
LOSS-OF-CHARGE/LOW-PRESSURE SWITCH
(Liquid Line) (psig)
Cutout
Reset (Auto)
RETURN-AIR FILTERS (in.)
Throwaway
* Based on altitude of 0 to 2000 ft.
UNIT
V-PH-HZ
SIZE 683B
024
208/230–1–60
030
208/230–1–60
036
208/230–1–60
042
208/230–1–60
048
208/230–1–60
060
208/230–1–60
TABLE 5—ICM FIOP PHYSICAL DATA—UNIT 683B (CONTINUED)
THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP
048090
4
409
10.6
.076
0.046 (2)
2...17
13.5
3300
22
1/4 (1100)
4...15
4.7
1600
11 X 10
3/4
3...38
3...46
24 X 30 X 1
TABLE 6—683B WITH ICM FIOP ELECTRICAL DATA
VOLTAGE
COMPRESSOR
RANGE
MIN
MAX
RLA
187
253
13.5
187
253
15.9
187
253
16.9
187
253
22.4
187
253
21.3
187
253
27.6
048115
048130
4
4
409
409
Scroll
1
10.6
10.6
.076
.076
0.046 (2)
0.046 (2)
2...17
2...17
13.5
13.5
3300
3300
22
22
1/4 (1100)
1/4 (1100)
4...15
4...15
4.7
4.7
1600
1600
11 X 10
11 X 10
3/4
3/4
3...33
3...31
3...42
3...41
610 ± 15
420 ± 25
20 ± 5
45 ± 10
24 X 30 X 1
24 X 30 X 1
OUTDOOR FAN
MOTOR
LRA
FLA
61.0
0.9
73.0
0.9
83.0
1.6
105.0
0.9
109.0
1.6
158.0
1.6
—16—
060090
060115
5
5
504
504
12.4
12.4
.088
.088
0.052 (2)
0.052 (2)
2...17
2...17
15.4
15.4
3300
3300
22
22
1/4 (1100)
1/4 (1100)
4...15
4...15
5.7
5.7
1750
1750
11 X 10
11 X 10
1.0
1.0
3...38
3...33
3...46
3...42
24 X 30 X 1
24 X 30 X 1
INDOOR FAN
POWER SUPPLY
MOTOR
MAX FUSE
FLA
MCA
OR CKT. BKR.
4.3
22.1
4.3
25.1
6.8
29.5
6.8
35.7
6.8
35.0
9.2
45.3
060130
5
504
12.4
.088
0.052 (2)
2...17
15.4
3300
22
1/4 (1100)
4...15
5.7
1750
11 X 10
1.0
3...31
3...41
24 X 30 X 1
30
35
40
50
50
60

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

583b602b683b

Table of Contents

Save Article as PDF