Download Print this page

Danfoss NovoCon Series Operating Manual page 2

Co6, energy, i/o high accuracy actuator

Advertisement

NovoCon® S CO6, Energy, I/O - High Accuracy Actuator
®
NovoCon S CO6, Energy, I/O
003Z8503
Actuator for AB-QM DN10-32
Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA
Power: 24VAC/DC, 50/60 HZ
Force: 90N. Stroke: 7 mm. Speed: 3-24s/mm
Consumption: 3.9VA running. Standby 0.9W
IP54/40, -10T55
Presettings
NovoCon® S
CO6, Energy, I/O
Safety Note
To avoid injury and damage to persons and
devices, it is absolutely necessary these
instructions are carefully read and observed
prior to assembly and commissioning.
Necessary assembly, start-up, and maintenance work
must be performed only by qualified, trained and
authorised personnel.
Switch off the power line before wiring the actuator.
Safety Note
Connect via safety isolating transformer.
Galvanic separations shall be provided for
segments crossing buildings.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2 | © Danfoss | DHS-SRMT/SI | 2017.05
®
NovoCon S CO6, Energy, I/O
003Z8503
E100 VXX
01
Actuator for AB-QM DN10-32
281624
Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA
6430 Nordborg, Denmark
0030471
Power: 24VAC/DC, 50/60 HZ
Force: 90N. Stroke: 7 mm. Speed: 3-24s/mm
Consumption: 3.9VA running. Standby 0.9W
III
IP54/40, -10T55
DIP Switch
1
2
DIP Switches 1 to 7 are used to assign the MAC address manually. Default MAC address assignment
method is Auto MAC addressing for BACnet MS/TP and DIP Switches for Modbus RTU.
For termination of last unit on the field bus, turn DIP Switch 8 ON.
Dip switch 9 is not used.
Dip switch 10 is used to select between BACnet MS/TP (OFF=Default) and Modbus RTU (ON).
When the protocol is changed on DIP Switch 10, a power cycle is required.
Application mode:
MSV:9 / 32810
Digital control (default),
Analog control,
CO6 mode,
Inverted CO6 mode
E100 VXX
Serial number can be removed from the
281624
6430 Nordborg, Denmark
NovoCon® S and added to installation drawing.
0030471
MADE IN SLOVENIA
MADE IN SLOVENIA
E100 VXX
E100 VXX
01
281624
281624
III
0030471
0030471
3
4
5
6
7
8
9
10
Select Valve Type
MSV:3 / 32802
(default AB-QM DN 15)
Safety Note
If the NovoCon® S network is supplied with
two or more AC power boosters, caution must
be observed when disconnecting one of the
transformers from the high voltage power
line. As the NovoCons are connected in a daisy chain,
there may be high voltage on the primary side of the
disconnected power supply. Disconnect always both
the primary and secondary side of the transformer.
Safety Note
Always follow the local disposal regulations.
01
Device Object
Instance Number
ON
OFF
Design Flow Rate
in Digital / Analog mode
AV:0 / 32768
in CO6 mode
AV:30 / 32796 Heating
AV:31 / 32798 Cooling
eady agreed.
73690660/VI.HU.I3.02

Advertisement

loading

This manual is also suitable for:

Novocon s003z8504