2) Address setting
a. One non-polarity controller can control up to 16 indoor units.
b. When the non-polarity controller is connected to several units, every air-conditioner in network has only one
network address to distinguish each other.
c. Address code of air-conditioner in LAN is set by code switch ENC1(Duct and Ceiling& Floor) or ADSS(Cassette)
of the indoor unit, and the set range is 0-15.
d. Note: The indoor units are controlled at the same time, not independently. The purpose of setting network
address is identify the unit when error occurs.
Page 90
Unit1
HA HB
HA HB
Wired controller
Unit2
HA HB
Unit16
HA HB