Midea MUE-18HRFNX-QRD0 Technical Manual page 101

Floor ceiling r32 50hz 3d inverter control
Table of Contents

Advertisement

The correct installation will not cause converse
water flow and the slope of the branch pipes can be
adjusted freely
The false installation will cause converse water flow
and the slope of the branch pipe can not be ad-
justed.
6. Water storage pipe setting
If the indoor unit has high extra static pressure and
without water pump to elevate the condensate wa-
ter, such as high extra static pressure duct unit , the
water storage pipe should be set to avoid converse
flow or blow water phenomena.
7. Lifting pipe setting of indoor unit with water pump
The length of lifting pipe should not exceed
750mm.
The drainage pipe should be set down inclined after
the lifting pipe immediately to avoid wrong opera-
tion of water level switch.
Refer the following picture for installation reference.
8. Blowhole setting
For the concentrated drainage pipe system, there
should design a blowhole at the highest point of
main pipe to ensure the condensate water discharge
smoothly.
The air outlet shall face down to prevent dirt enter-
ing pipe.
Each indoor unit of the system should be installed it.
The installation should be considering the conve-
nience for future cleaning.
9. The end of drainage pipe shall not contact with ground
directly.
5.3
Insulation work of drainage pipe
Refer the introduction to the insulation engineering
parts.
Page 101