Download Print this page

Installation; Warranty - Siemens QAW910 Manual

Room unit
Hide thumbs Also See for QAW910:

Advertisement

Installation

Note
Commissioning
Maintenance /
battery change
Disposal

Warranty

Technical data
Power supply
RF
Temperature sensor
Display
Standards
Building Technologies
HVAC Products
Mounting with the base:
The QAW910 can be fitted to most commercially available recessed conduit boxes or
directly on the wall.
Mount the QAW910 first and then insert the batteries.
Prior to commissioning, check to ensure that the QAW910 is correctly fitted to the wall
and that the batteries are correctly inserted.
The QAW910 is maintenance-free.
The system indicates when batteries must be replaced. The batteries are located in the
battery compartment. Batteries can be changed without removing the sensor from the
wall and there is no need for using tools (reversed polarity protection).
In terms of disposal, the QAW910 is classified as electronic scrap conforming to the
European Directive 2002/96/EG (WEEE) and must not be disposed of as domestic
waste. The relevant national legal regulations must be complied with. The unit must be
disposed of through the relevant channels. Local and currently valid legislation must be
observed. Exhausted batteries must be disposed of in compliance with environmental
regulations.
Application-related technical data are only warranted in connection with the Siemens
Synco 900 system. For equipment combinations, refer to the Data Sheet of the central
apartment unit.
When using the QAW910 together with third-party devices, correct functioning
must be ensured by the user. In that case, Siemens will assume no responsibility
for service and warranty.
Type of battery
Battery life (capacity ≥ 2.5 Ah)
Frequency
Range
Protocol
Sensing element
Measuring range
Time constant
Type
Resolution
conformity to
EEC directive
- Immunity
- Emissions
Low-voltage directive
- Electrical safety
RTTE Radio & Telecom. Equipment
Radio communication
Room unit QAW910
2 x alkaline batteries LR6 (AA) 1.5 V
3 years
868 MHz (bidirectional)
typically 30 m inside buildings
KNX RF compatible
NTC 10 kOhm
0...50 °C
20 minutes
segment LCD
0.1 °C
89/336/EC
- EN 61000-6-1/2
- EN 61000-6-3/4
73/23/EC
- EN 60730-1
99/5/EEC
- EN 300220-1, EN 300220-3, EN 301489-3
5/6
CE1N2703en
11.07.2006

Advertisement