Daikin RZQ20KCVJK Installation Manual page 26

Split system air conditioner
Table of Contents

Advertisement

Available languages

Available languages

01_EN_3P281953-1B.fm Page 25 Tuesday, January 25, 2011 3:35 PM
〈 Connection information on power supply wiring, earth wiring, and transmission wiring 〉
For the indoor unit wiring and transmission wiring (dash lines in the drawing), follow the instructions in the
indoor unit's installation manual.
Use 125 or 140 type shield cable for the transmission wiring, and be sure to earth the shield wire.
VJK
Branch switch,
overcurrent
breaker
Remote Controller
〈 Specification of standard wiring components 〉
RZQ
Minimum circuit amps (MCA)
Recommended field fuse (A)
NOTES
1. Order appropriate power wire while following national laws and standards for the insulating sheath,
thickness, and length.
2. When installing wiring in a location that can easily come in contact with people, be sure to install an earth
leakage breaker to prevent electric shock.
3. The earth leakage breaker must be a high-speed type breaker of 30mA(<0.1S).
4. Use an earth leakage breaker that can also be used as earth leakage, overload, short-circuit protection.
Be sure to use earth leakage breakers dedicated for earth leakage protection in combination with the load
break switch with fuse or breaker for wiring.
〈 CAUTION 〉
To the electrician
Do not run the unit until the refrigerant piping is complete, as not waiting could break the compressor.
25
POWER SUPPLY
230V
60Hz
L
N
Earth leakage
breaker
1 2 3
L N
O
U
T
D
O
O
R
U
N
T I
1 2 3
INDOOR UNIT
VJK
20
24
18.8
20
YAK
POWER SUPPLY
L1 L2 L3
Earth leakage
Branch switch,
breaker
brea
overcurrent
breaker
L1 L2 L3 N
1 2 3
O
1 2 3
INDOOR UNIT
Remote Controller
YAK
36
45
45
48
28.2
16.7
30
20
400V
3N~
60Hz
N
U
T
D
O
O
R
U
N
T I
English