PZE X4VP
}
Earth fault in the feedback loop:
Detected, depending on the base unit that is used.
}
Earth fault in the input circuit:
The output relays deenergise and the safety contacts open.
Block diagram/terminal configuration
*Insulation between the nonmarked area and the relay contacts: Basic insulation (over
voltage category III), Protective separation (overvoltage category II)
Function description
The contact expansion module is an addon device with delayon deenergisation, and it is
used to expand a safety circuit. The contact expansion module is driven by a base unit (e.
g. emergency stop relay).
}
Functional procedure after closing the safety contacts of the base unit:
–
–
–
}
Functional procedure after opening the safety contacts of the base unit:
–
–
–
Installation
}
The unit should be installed in a control cabinet with a protection type of at least IP54.
}
Use the notch on the rear of the unit to attach it to a DIN rail.
}
Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing ele
ment (e.g. retaining bracket or an end angle).
Operating Manual PZE X4VP
1003202EN08
A1 A2
=
Input
=
Power
The supply voltage is present at the input (A1) of the contact expansion module.
Close the safety contacts 1718, 2728, 3738 and 4748.
The LEDs "CH. 1" and "CH. 2" are lit.
There is not supply voltage at input (A1) of the contact expansion module.
Safety contacts 1718, 2728, 3738 and 4748 open after the delay time.
The LEDs "CH. 1" and "CH. 2" go out.
*
Y1
17 27 37
47
K1
K2
Y2
18 28 38
48
A1
17
27
37
P1
PNOZ X4VP 3s
PZE X4VP
CH.1
CH.2
17
27
37
47
18
28
38
48
P2
Y1 Y2 47
48
P1
A2
18
28
38
6