Remove Plug­in Terminals; Order Reference - Pilz PZE X4VP Operating Manual

Safety relays
Hide thumbs Also See for PZE X4VP:
Table of Contents

Advertisement

PZE X4VP
}
Contact service life: 1,000,000 cycles
Provided the application requires fewer than 1,000,000 cycles, the PFH value (see tech­
nical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With contact­
ors, use freewheel diodes for spark suppression.
Remove plug­in terminals
Procedure: Insert the screwdriver into the housing recess behind the terminal and lever the
terminal out.
Do not remove the terminals by pulling the cables!
Order reference
Type
PZE X4VP
PZE X4VP C 24 V DC; t
PZE X4VP
PZE X4VP C 24 V DC; t
PZE X4VP
PZE X4VP C 24 V DC; t
Operating Manual PZE X4VP
1003202­EN­08
Features
Connection type
24 V DC; t
= 0.5 s Screw terminals, plug­in
= 0.5 s Spring­loaded terminals, plug­in
24 V DC; t
= 1 s
Screw terminals, plug­in
= 1 s
Spring­loaded terminals, plug­in
24 V DC; t
= 2 s
Screw terminals, plug­in
= 2 s
Spring­loaded terminals, plug­in
Order no.
777580
787580
777581
787581
777582
787582
19