Pilz PZE X4VP Operating Manual

Pilz PZE X4VP Operating Manual

Safety relays
Hide thumbs Also See for PZE X4VP:

Advertisement

Quick Links

PZE X4VP
}
Safety relays
Operating Manual-1003202-EN-12

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PZE X4VP and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Pilz PZE X4VP

  • Page 1 PZE X4VP Safety relays Operating Manual-1003202-EN-12...
  • Page 2 Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
  • Page 3: Table Of Contents

    ........................Faults – Interference ......................Dimensions in mm ......................... Technical details ........................Safety characteristic data ......................Supplementary data ......................Service life graph ........................Remove plug-in terminals ..................... Order reference ........................EC declaration of conformity ....................Operating Manual PZE X4VP 1003202-EN-12...
  • Page 4: Introduction

    PZE X4VP Introduction Validity of documentation This documentation is valid for the product PZE X4VP. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
  • Page 5: Safety

    Safety Intended use The contact expansion module PZE X4VP meets the requirements of EN 60947-5-1 and EN 60204- 1. It is an expansion module for increasing the number of contacts available on a base unit. Base units are all safety relays with feedback loop.
  • Page 6: Use Of Qualified Personnel

    Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120 VDC) are present on the unit, connected control elements and sensors must have a rated insulation voltage of at least 250 V. Operating Manual PZE X4VP 1003202-EN-12...
  • Page 7: Unit Features

    Earth fault in the input circuit: The output relays de-energise and the safety contacts open. Block diagram/terminal configuration *Insulation between the non-marked area and the relay contacts: Basic insulation (over- voltage category III), Protective separation (overvoltage category II) Operating Manual PZE X4VP 1003202-EN-12...
  • Page 8: Function Description

    PZE X4VP Function description The contact expansion module PZE X4VP is an add-on device with delay-on de-energisa- tion, and it is used to expand a safety circuit. The contact expansion module is driven by a base unit (e. g. emergency stop relay).
  • Page 9: Wiring

    (SELV, PELV) in accordance with VDE 0100, Part 410. Preparing for operation Supply voltage 24 V DC Input circuit Single-channel Dual-channel Base unit: 24 V DC Safety relay PNOZ X Driven via safety contacts Operating Manual PZE X4VP 1003202-EN-12...
  • Page 10: Operation

    Open circuit, short circuit or earth fault ( e.g. in the input circuit) In the case of an error, the delay-on de-energisation safety contacts may open before the delay time has elapsed. Operating Manual PZE X4VP | 10 1003202-EN-12...
  • Page 11: Dimensions In Mm

    50 ms 100 ms 140 ms Inputs 777580 777581 777582 Number Voltage at Input circuit DC 24 V 24 V 24 V Current at Input circuit DC 95 mA 95 mA 95 mA Operating Manual PZE X4VP | 11 1003202-EN-12...
  • Page 12 24 V DC G. U. With current Pilot Duty B300, R300 B300, R300 B300, R300 External contact fuse pro- tection, safety contacts In accordance with the standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1 Operating Manual PZE X4VP | 12 1003202-EN-12...
  • Page 13 93 % r. h. at 40 °C Condensation during op- eration Not permitted Not permitted Not permitted EN 60947-5-1, EN EN 60947-5-1, EN EN 60947-5-1, EN 61000-6-2, EN 61326-3-1 61000-6-2, EN 61326-3-1 61000-6-2, EN 61326-3-1 Operating Manual PZE X4VP | 13 1003202-EN-12...
  • Page 14 Stripping length with screw terminals 8 mm 8 mm 8 mm Dimensions Height 94 mm 94 mm 94 mm Width 22,5 mm 22,5 mm 22,5 mm Depth 121 mm 121 mm 121 mm Operating Manual PZE X4VP | 14 1003202-EN-12...
  • Page 15 787581 Number of output con- tacts Safety contacts (N/O), delayed Max. short circuit current 1 kA 1 kA 1 kA Utilisation category In accordance with the standard EN 60947-4-1 EN 60947-4-1 EN 60947-4-1 Operating Manual PZE X4VP | 15 1003202-EN-12...
  • Page 16 66 A²s Blow-out fuse, quick Blow-out fuse, slow Blow-out fuse, gG Circuit breaker 24 V AC/DC, characteristic Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au Operating Manual PZE X4VP | 16 1003202-EN-12...
  • Page 17 EN 60947-1 Overvoltage category III / II III / II III / II Pollution degree Rated insulation voltage 250 V 250 V 250 V Rated impulse withstand voltage 4 kV 4 kV 4 kV Operating Manual PZE X4VP | 17 1003202-EN-12...
  • Page 18 101 mm Width 22,5 mm 22,5 mm 22,5 mm Depth 121 mm 121 mm 121 mm Weight 210 g 185 g 190 g Where standards are undated, the 2020-07 latest editions shall apply. Operating Manual PZE X4VP | 18 1003202-EN-12...
  • Page 19 1500 VA DC1 at 24 V 24 V Min. current 0,01 A 0,01 A Max. current Max. power 150 W 150 W Utilisation category In accordance with the standard EN 60947-5-1 EN 60947-5-1 Operating Manual PZE X4VP | 19 1003202-EN-12...
  • Page 20 55 ms With automatic start after power on max. 200 ms 200 ms Delay time tv Time accuracy -50 %/+50 % -50 %/+50 % Supply interruption before de-ener- gisation 1.000 ms 1.500 ms Operating Manual PZE X4VP | 20 1003202-EN-12...
  • Page 21 Stripping length with spring-loaded terminals 8 mm 8 mm Dimensions Height 101 mm 101 mm Width 22,5 mm 22,5 mm Depth 121 mm 121 mm Weight 205 g 210 g Operating Manual PZE X4VP | 21 1003202-EN-12...
  • Page 22: Safety Characteristic Data

    A safety function's SIL/PL values are not identical to the SIL/PL values of the units that are used and may be different. We recommend that you use the PAScal software tool to calculate the safety function's SIL/PL values. Operating Manual PZE X4VP | 22 1003202-EN-12...
  • Page 23: Supplementary Data

    DC-1: 24V AC-1: 230V AC-1: 230V AC-15: 230V AC-15: 230V DC-13: 24V DC-13: 24V 3 4 5 6 8 10 Switching current (A) Fig.: Service life graphs at 24 VDC and 230 VAC Operating Manual PZE X4VP | 23 1003202-EN-12...
  • Page 24 To increase the service life, sufficient spark suppression must be provided on all relay con- tacts. With capacitive loads, any power surges that occur must be noted. With DC contact- ors, use flywheel diodes for spark suppression. Operating Manual PZE X4VP | 24 1003202-EN-12...
  • Page 25: Remove Plug-In Terminals

    Order no. type PZE X4VP 24 V DC; t = 0.5 s Screw terminals, plug-in 777580 PZE X4VP C 24 V DC; t = 0.5 s Spring-loaded terminals, plug-in 787580 PZE X4VP 24 V DC; t = 1 s Screw terminals, plug-in 777581 PZE X4VP C 24 V DC;...
  • Page 26: Ec Declaration Of Conformity

    European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/support/downloads. Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ost- fildern, Germany Operating Manual PZE X4VP...
  • Page 27 We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters. Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com, Internet: www.pilz.com...