Interface characteristics
Rated & operational voltage (Un / Ue)
230V a.c. 50Hz
Rated insulation voltage (Ui)
320V a.c. 50Hz
Rated impulse withstand voltage (Uimp)
4kV
Rated current of the Assembly (InA)
40A
Note: Dependent upon rating of main incoming device
Rated current of an Outgoing circuit (Inc)
MCB 6A - 40A (marked rated current on device)
Rated conditional short-circuit current of the ASSEMBLY (Icc)
Annex ZB: 16 kA rms at 250V, power factor 0.6 with equipment and arrangements speci ed in Hager's technical documentation /
catalogue.
Protection against electric shock
Consumer unit shall be installed in an electrical system conforming to the current edition of IEC 60364 / BS 7671
Rated diversity factor (RDF) / Values of assumed loading
2way = 0.8
Rated frequency (fn)
50 Hz
Pollution degree
3
Types of system earthing for which the ASSEMBLY is designed
TNC-S, TN-S when installed in an electrical installation complying with BS 7671
Indoor or outdoor use -25'c
Stationary ASSEMBLY
Degree of protection
IP55 (VE24AH) with Door closed and full compliment of outgoing devices and or blanks fitted. Note: Where
cables are installed through top wall of enclosure, IP rating to be maintained.
Intended use
Intended for use in garages or similar premises.
Electromagnetic compatibility (EMC) classification
EMC Environment B
External design
VE : Wall-mounted, surface type, enclosed assembly.
Mechanical impact protection
IK 07
The type of construction
Fixed parts
Type A DBO (Distribution board for use by ordinary persons)
Hager Technical Help Line: 01952 675 689
Hager Technical Fax: 01952 675 557
Website: www.hager.co.uk
E-mail us: info@hager.co.uk
2
Note: RDF only applies to continuously and simultaneously loaded
circuits.
In principle, this means adjacent circuit-breakers having a load
'on' time exceeding 30 minutes or where a load not exceeding 30
minutes has an 'off' time less than the 'on' time, will need to have
the rated diversity factor applied as indicated.
ZD0630 - Issue 6 01-21