oventrop 1152451 Installation And Operating Instructions Manual page 5

Table of Contents

Advertisement

Available languages

Available languages

3
Transport, storage and packaging
3.1
Transport inspection
Upon receipt, check delivery for any damages caused during
transit.
Any damages must be reported immediately upon receipt.
3.2
Storage
Please remove protective foil of the display and any transport
protections only immediately before installation.
Please protect room thermostat against external forces (e.g.
impacts, vibrations etc.).
The room thermostat must only be stored under the following
conditions:
• Do not store in open air, keep dry and free from dust.
• Do not expose to aggressive fluids or heat sources.
• Protect from direct sunlight and mechanical agitation.
• Storage temperature: 0°C up to 40°C,
max. relative humidity of air: 95 %
3.3
Packaging
All packaging material must be disposed of environmentally
friendly.
4
Technical Data
4.1
Performance data
Temperature setting range:
Switching temperature
difference:
Operating voltage:
Switching current:
Power:
Fuse:
Service life:
Protection:
4.2
Dimensions / Connection dimensions
Illustr. 4.1 Dimensions
5 to 35°C
about ±1K
- Item no.: 1152451
85-260 V AC, 50/60Hz
- Item no.: 1152452
24 V AC, 50/60Hz
2 (1) A
< 3 W
3 A, 250 V
> 100.000 relay actuated switching
operations
IP 30
5
Construction and function
Illustr. 5.1 Display and functions of press buttons
5.1
Functional description
The digital room thermostat is used for the fan drive of Fan-Coil
units. The temperature of the fan convectors is controlled
continuously with the help of a valve which is activated through
an actuator. When the temperature has reached the set nominal
value, the valve is closed and the ventilator keeps running.
Setting of the nominal value by key stroke, visualisation on a
large LCD display with blue backlighting. The backlighting is
active when pressing the keys.
Operating functions: Heating, cooling, ventilation.
Fan speeds: slow, medium, fast or automatic.
Settings can be stored. Valve and Fan-Coil unit relay-controlled.
5.2
Application range
The digital room thermostat is suitable for the operation with
three-speed fans in combination with Oventrop two point
actuators.
6
Installation and assembly
6.1
Extent of supply
Before installing the room thermostat, please check delivery for
completeness and any damages caused during transit.
6.2
Installation
Switch off current supply.
Do not apply pressure onto the display during installation!
85-260 V AC (Item no. 1152451)
Illustr. 6.1 Wiring diagram 85-260 V / 24 V
24 V AC (Item no. 1152452)
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

1152452