Recommendations For Installing The Hoses; Condensate Drainage; Installing The Humidity Or Indoor Air Quality Sensors - VENTILAIRSEC VMI PUREVENT Installation And Maintenance Manual

Table of Contents

Advertisement

Available languages

Available languages

Regardless of the block diagram chosen, the following rules must be applied:
Thermostatic valve
None
One or more
On all transmitters

3.5.6 Recommendations for installing the hoses

The Hydro'R module is connected to the heating network at the tapping point via the insulated
hydraulic hoses (if the VMI® is not installed in a heated area). Implementation of the hoses must
comply with best practices to avoid causing any pressure drop in the hydraulic system.

3.5.7 Condensate drainage

Prior to commissioning, the Hydro'R module must be connected to a waste water network.
-
unit.
-
connector under the Hydro'R module.
-
secure using a hose clamp.
-
RECOMMENDATION
Before any commissioning of the VMI®, it is essential to fill the siphon with water
inside the Hydro'R loop (10 cl minimum).

3.5.8 Installing the humidity or indoor air quality sensors

Make sure to refer to the installation instructions provided with the sensor.
3.5.8.1
Sensor installation location
3.5.8.1.1
Preferred locations within a domestic or commercial environment
The recommendation is to install the sensor:
-
At least 1 metre from the ground if the sensor is placed on furniture or on a shelf (using the
removable stand supplied with the INSAFE+ Carbon model)
-
At least 1.5 metres from the ground if the sensor is wall-mounted (attached with screws and
wall plugs)
To obtain data as close as possible to the user, we advise sticking to the recommended locations.
Actions possible
in the circulation pump
Increase in speed
No actions
No actions
Install the pneumatic coupling and its gasket on the VMI®
The pipe supplied should be connected to the pneumatic
To create a siphon effect, create a loop with the pipe and
Connect the drain pipe to the waste water network.
Possible balancing of system
Tighten the adjustment tee fitting on
each transmitter
Tighten the adjustment tee fitting on
each transmitter without a thermostatic
valve
Tighten the adjustment tee fitting on
each transmitter
Ensure that a differential pressure control
valve is correctly installed
35