CO NF IG UR AT IO N O F FC610
5

Configuration

5.1

Configuration of FC610

Parameters of FC610 are expected to be configured via HMI panel MP53 or MP56 which is de-
scribed in section 4.
In case of firmware updating or reading event curves, MConfig-G software must be used.
MConfig-G establish communication with FC610 via RS485 communication which is shown be-
low. A dedicated parameterization cable TK202 is required to connect FC610 and the configu-
ration computer with the MConfig-G software installed.
It is also possible to configure FC610 via communication. Please refer to "1TNC928247 FC610
Modbus Protocol Implementation" for more information.
5.2

Factory default setting

For an easy startup of FC610, the following factory settings are preloaded in the device.
Parameters
Feeder Information
Feeder ID
System supply voltage
Frequency
Feeder type
Feeder power rating
Feeder nominal current
Feeder Control
Feedback Function
External CT Primary
External CT Secondary
1T N C928 25 0M0 201

Figure 36: Configuration of FC610

Range
110-50000 V
50/60 Hz
Single phase/3- phase
/3-phase+N
Current feedback/main switch
feedback*
CO NF IG UR AT IO N
Factory setting
na
380 V
50 Hz
3-phase+N
1.5 kW
5 A
Current Feedback
1
1
48