Advertisement

Electromagnetic environment
Pollution degree
EMC compatibility
Electrostatic discharge
Electromagnetic field immunity
Conducted disturbance immunity
Burst immunity
Surge immunity
Voltage dip
Short interruption
Power frequency magnetic field
Radiated disturbance
Standards
1T N C928 25 0M0 201
1) Equipment in the system comply with EMC
requirement of CE / CCC certificate.
2)
Power
supply
system
IEC61000-2-1, IEC61000-2-2, especially the sys-
tem in which VSD / Frequency Converters are
used.
2
4.0 kV contact discharge
8.0 kV air discharge (IEC61000-4-2)
10 V/m (80-1000 MHz), 3 V/m (1.4-2 GHz), 1 V/m
(2-2.7 GHz) (IEC61000-4-3)
3V (150 kHz to 80 MHz) (IEC61000-4-6)
2 kV(5/50 ns, 5 kHz) for AC power and DC power
1 kV(5/50 ns, 5 kHz) for I/O signal control
(IEC 61000-4-4)
1 kV/2 kV (IEC 61000-4-5)
0 % during 1 cycles
40 % during 10/12 cycles
70 % during 25/30 cycles
(IEC61000-4-11)
0 % during 250/300 cycles (IEC61000-4-11)
30 A/m (50 Hz, 60 Hz) (IEC61000-4-8)
EN55011/CISPR 11, Class A
IEC 61557-12:
class 0.5
GB/T 18216.12: class 0.5
CO NF IG UR AT IO N
complies
with
5 2