A .1 T ECHN I CA L SP ECI FI CATI O NS
Auxiliary power supply
Rated operational voltage (Ue)
Voltage operation range
Rated frequency
Power consumption
Power output
Current
Voltage
Terminal wire area
Recommended tightening torque
Relay output
Rated operation voltage (Ue)
Rated operation current (Ie)
Digital inputs
Voltage
On
Off
Terminal wire area
Recommended tightening torque
Communication
Terminal wire area
Recommended tightening torque
Modbus-RTU
Environmental
Operating temperature
Storage temperature
Humidity
Derating accepted operating altitude
Without derating operating altitude
Resistance to water and dust
Mechanical environment
1T N C928 25 0M0 201
110-240 VAC
85 %-110 % Ue
50 / 60 Hz
16 VA max. @ 240 VAC
8 VA max. @ 110 VAC
100 mA @ 240 VAC supply input
50 mA @ 110 VAC supply input
24 VDC
2
0.2 .. 2.5 mm
0.5 .. 0.6 Nm
24 or 110 VDC, 110 or 240 VAC
2A /24 VDC(DC-13)
0.1A/110 VDC(DC-13)
4A/120 VAC(AC-15)
2A/240 VAC(AC-15)
24 VDC
Voltage: 15 V < V < 30 V, current: 2 mA < I < 15
mA
Voltage: 0 V < V < 5 V, current: 15 mA max
0.2 .. 2.5 mm
2
0.5 .. 0.6 Nm
2
0.2 .. 2.5 mm
0.5 .. 0.6 Nm
Up to 115.2 kbps
-5 ℃ - 55 ℃
-40 ℃ - 85 ℃
15 % up to 95 % without dew
4500 m
2000 m
HMI MP53/56: IP54
Main unit:
IP20
Vibration 10 Hz-150 Hz, 1 g
Shock 11 ms, 15 g