Feature
Current Protection Functions
Cold Load and Inrush Blocking
Convenient Dashboard View
Self-Supervision
Security Log
Role Based Access
Firmware Upgrade
Simple, platform-independent, web browser based intuitive interface
Description
Three selectable delayed curves (50/51P) with time dial, time delay, and blocking
– ANSI/IEEE curves and Definite Time
– Recloser Curves (Electronic and Hydraulic)
– Fuse Curves
– Custom Curves
Cold Load Pickup and Inrush Inhibit (2nd Harmonic) feature available for each curve
– Bird's eye view on device status
– Carry out operations right from the dashboard
– Single Line Diagram with recloser status
– Compatible with all web browsers on all platforms including hand-held devices
Operation counter, diagnostics and wear monitoring alarms
Record of logins, changes, and unauthorized access attempts
Permissions based on user roles
(1) Viewer – Log on and view status
(2) Operator – Operate the unit
(3) Engineer – Setting changes
(4) Administrator – Access Management
Simple and secure firmware upgrade over Wi-Fi