GOK GS Pro-Fi 3 Assembly And Operating Manual page 18

Combined heating oil filter breather type
Hide thumbs Also See for GS Pro-Fi 3:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 13
Determination of the flow rate w in m/s
Installation in
.
=
V
Volume flow rate
Operating medium
(L/h)
For oil consumer installations, the following mean flow rate is applicable pursuant to
DIN 4755:
Taking into account the length of the suction
line, the geodesic height, the suction height, and
the fuel oil volume flow rate, the following can
be recommended for selecting the piping:
• Lower flow rates in suction mode will result in an undesired formation of bubbles.
• Piping with inner diameters (ID) of less than 4mm is not recommended!
Maximum total pressure loss of all fittings in the suction line = 0.4bar
The pressure loss of the GS Pro-Fi 3 depending on the fuel oil volume flow rate and the filter
insert used can be found in the diagram:
Filter insert
There is no such thing as a universal filter insert. The filter insert should be selected
based on the specifications of the burner manufacturer according to filter mesh and
the present operating conditions.
Regarding oil consumer installations with so-called "Low-NOx burners" and burners
with lower heat outputs, the GOK filters "opticlean 2.0" (fine filtration) with a mesh
width of < 35μm are recommended.
6 / 12
Combined heating oil filter breather type GS Pro-Fi 3
Single string
system
Heat input
in kW / 10
Suction: (0.2 ÷ 0.5) m/s
:
Double string
system
=
Gear output of the
Oil burner pump
.
V Fuel oil
(1 ÷ 10) l/h
(8 ÷ 45) l/h
(25 ÷ 130) l/h
(90 ÷ 170) l/h
Conveyor
Calculation
system
=
w = 0.3537 •
Delivery rate
ID= pipe inner
of the booster
diameter (mm)
pump
Discharge: (1.0 ÷1.5) m/s
*AD x t Copper pipe
6 x 1mm
8 x 1mm
10 x 1mm
12 x 1mm
*AD ( outer diameter)
Part no. 13 512 53 b
.
/ ID
2
V