F4 Discharge Temperature Sensor Error - Toyotomi KURO Mini Service Manual

Table of Contents

Advertisement

TOYOTOMI
U-Match 5 SERIES UNIT SERVICE MANUAL
Troubleshooting:
Note:Please refer to Appendix 1 for the relation between temperature and resistance of temperature sensor.
3.4.12 ―F4‖ Discharge Temperature Sensor Error
Error display: ODU mainboard, IDU wired control and IDU receiver light board will display
F4
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the range of AD value, If
the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report the error.
Possible reason:
■Poor contact between temperature sensor and terminal in mainboard interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal
52