DVC6200 or DVC2000 Digital Valve
Controller on 657 and 667, Size 80
Actuators (up to 2 inch travel)
8. Attach the digital valve controller to the mounting
bracket and tighten the three hex head cap screws
(key 1b).
9. Check the position of the magnet assembly (key 3)
in the channel of the digital valve controller housing and
ensure that it is visually centered between the channel
walls and has adequate clearance with the backside of
the channel (approximately 3 mm).
10. Calibrate the digital valve controller as described in
the instruction manual or quick start guide.
For additional information concerning the mounting,
setup, calibration and maintenance of the DVC6200 or
DVC2000 digital valve controller, refer to the
appropriate instruction manual.
Note
Neither Emerson, Emerson Process
Management, nor any of their affiliated
entities assumes responsibility for the
selection, use or maintenance of any
product. Responsibility for the selection,
use and maintenance of any product
remains with the purchaser and end user.
1b
USER TO SELECT ORIENTATION AND SLOT BASED ON ACTUATOR REQUIREMENT.
1
GG06217
Figure 2. Mounting Parts Identification; Up to 2 Inch Travel
Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Process
Management business division of Emerson Electric Co. Emerson Process Management,
Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co.
All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they
are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the
designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, nor any of their affiliated
entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of
any product remains solely with the purchaser and end user.
Emerson Process Management
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Chatham, Kent ME4 4QZ UK
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
2
EFisher Controls International LLC 2010; All Rights Reserved
FIGURE SHOWS MAGNET ASSEMBLY
MARKING ALIGNED WITH SENSOR
INDEX MARK FOR AIR-TO-EXTEND
ASSEMBLY MARKING
NOTE:
DURING THE COMPLETE STROKE OF THE
ACTUATOR, AT ANY PARTICULAR POSITION,
THE DIGITAL VALVE CONTROLLER HALL
SENSOR MUST REMAIN WITHIN THE MARKING
SHOWN ON THE MAGNET ASSEMBLY
7
4
8
5
6
Mounting Instructions
D103445X012
Figure 1. Alignment Template
1a
2
3
1c
MAGNET ASSEMBLY
May 2010