ICM/ICAD Motorized Valve
Wiring diagram showing ICAD wired with
a PLC or other type of third-party
electronics
Note:
The ICAD supplies the power for the 4-20 mA
feedback signal.
Wiring diagram with Danfoss EKC
controllers
Note:
For instructions on completely wiring an EKC
controller, please see the relevant EKC
controller manual.
6
Installation, Programming, and Troubleshooting
Terminal box is customer supplied.
Terminal box is customer supplied.
DKRCI.EI.HT0.A1. / 50H1639
PLC
+
Active 4-20 mA PLC output to control ICAD
-
Active 4-20 mA PLC output to control ICAD
Gray
Yellow
-
Passive 4-20 mA PLC input
for valve position feedback
Blue
+
Passive 4-20 mA PLC input
for valve position feedback
White
Brown
Green
Yellow (ground)
(+ 4-20 mA)
Gray
Blue (+ 4-20 mA)
Optional position
feedback
Only possible
with EKC 347
+
Optional UPS/battery back up
White
Brown
Green
+
Optional UPS/battery back up
24 V d.c
+
Power
-
Supply
CUSTOMER SUPPLIED
24 V d.c
+
Power
-
Supply
CUSTOMER SUPPLIED