V9055A,D MODULATING FLUID POWER GAS VALVE ACTUATOR

SPECIFICATIONS

Models:
V9055A: Modulating Fluid Power Gas Valve Actuator.
V9055D: Modulating Fluid Power Gas Valve Actuator with
proof-of-closure switch.
Model
STANDARD PRESSURE VALVES
V5055A, B, C, F, V5097A, B, C
HIGH PRESSURE VALVES V5055D,
E, V5097D, E
a
Max Operating Pressure Differential (UL) or Max Operating Pressure (CSA); maximum allowable pressure drop from inlet to
outlet for proper operation.
b
Max rated pressure (UL) or Max Close-off Pressure (CSA); maximum pressure that the valve can be exposed to without leak-
age or damage to the valve.
c
Applies for small-body V5097 valves 3/4" up to 2" pipe size.
d
Applies for large-body V5097 valves 2" up to 3" pipe size.
e
V5055A, B, C only.
Table 2. Electrical Ratings.
Opening
Voltage/
Frequency
Watts
120/60
60
122
100-50/60
57/46
100/81
220/50
68
141
240/50
88
194

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
60-2311-11
Table 1. Pressure Ratings of Actuator-Valve Combinations.
Pipe Size
c
3/4" to 1-1/2"
d
2" to 3"
e
4" flanged
c
3/4" to 1-1/2"
d
2" to 3"
Holding
VA
Watts
VA
20
32
25/20
36/31
20
32
19
36
Low-Fire Adjustment: 0.14 inch to 0.65 inch (with respect
to V5055/V5097B Valve) valve stem travel. Refer to form
70-8311 for valve flow (capacity) curves.
STANDARD PRESSURE ACTUATORS V9055A, D
a
M.O.P.D.
5 PSI
340 mbar
5 PSI
340 mbar
3 PSI
207 mbar
5 PSI
340 mbar
5 PSI
340 mbar
Table 3. Auxiliary and Proof-of-Closure
Switch Ratings: 1/2 hp
Full Load
Locked Rotor
a
Maximum total connected power to both switches (if used) is
1800 VA.
Opening Time:
50 Hz models: 32 seconds (nominal).
60 Hz models: 26 seconds (nominal).
Closing Time: 1 second (maximum)
2
Max. Rated Pressure
15 PSI
1.0 Bar
15 PSI
1.0 Bar
15 PSI
1.0 Bar
75 PSI
5.0 Bar
45 PSI
3.0 Bar
a
.
120V
240V
9.8A
4.9A
58.8A
29.4A
b