Accel and Decel (733BDC)
Accel - The Accel trimpot is adjustable from 0-10 second of maximum output speed setting. The setting
of the accel time is approximately proportional to the rotation of the Accel trimpot. As an example, a
50% setting of the Accel trimpot will result in approximately a 5 second linear accel ramp from zero to
maximum speed. To test a setting, turn the speedpot to zero (fully CCW). Next turn the Accel trimpot
CW to the estimated accel setting. Quickly rotate the speedpot full CW and time the motor accel ramp
from zero to maximum speed. If necessary, adjust the Accel trimpot setting as needed and test again.
Decel - The Decel trimpot is adjustable from 0-10 second of maximum output speed setting. The
setting of the decel time is approximately proportional to the rotation of the Decel trimpot. As an
example, a 50% setting of the Decel trimpot will result in approximately a 5 second linear decel ramp
from maximum to zero speed. To test a setting, turn the speedpot to maximum (fully CW). Next turn
the Decel trimpot CW to the estimated decel setting. Quickly rotate the speedpot full CCW and time
the motor decel ramp from maximum to zero speed. If necessary, adjust the Decel trimpot setting as
needed and test again.
Note: Minumum, Maximum and Gain trimpot settings must already be completed to properly set and
test Accel and Decel. Refer to the Open Loop and Closed Loop Trimpot sections above for Minimum
Speed (MIN), Maximum speed (MAX), Current Limit (CUR LIM) and Gain trimpot adjustments.
Dart recommends not letting the heatsink temperature rise above 75
shipped from the factory, will normally handle up to 7.5 Amps continuous current. With the use of
the -HS2 optional heat sink, 9.0 Amps continuous current is achievable. If the ambient temperature
increases above 25
C. (77
o
temperature from exceeding 75
exceed the rated current.
INPUT VOLTAGE (JUMPER SELECTABLE) ................................................... 11 to 15VDC OR 18 to 54VDC
OUTPUT VOLTAGE ........................................................................................................ 0 to INPUT VOLTAGE
MOTOR HALL SPACING - ELECTRICAL (JUMPER SELECTABLE) ......................................... 60
LOAD CURRENT (CONTINUOUS) .................................................................................................. 7.5 AMPS
LOAD CURRENT USING -HS2 (CONTINUOUS) ............................................................................. 9.0 AMPS
SPEED RANGE ....................................................................................................................................... 50 : 1
MINIMUM SPEED TRIMPOT ......................................................................... ADJUSTABLE 0-30% OF MAX.
CURRENT LIMIT TRIMPOT ...................................................................................................... ADJUSTABLE
OPEN LOOP SPEED REGULATION ...................................................................... (MODEL 730BDC) NONE
INPUT / OUTPUT CONNECTIONS ........................................................... 14 POSITION TERMINAL BLOCK
INPUT / OUTPUT CONNECTIONS USING -P OPTION ....................................... 14 POSITION PLUGGABLE
SPEED COMMAND SIGNAL ....................... 5K Ohm SPEED POTENTIOMETER or 0 to +5V DC SIGNAL
OPERATING TEMPERATURE .......................................................................
CLOSED LOOP SPEED REGULATION ............. (MODEL 731BDC and 733BDC) ± 1/2% OF BASE SPEED
MAXIMUM SPEED TRIMPOT ............................................. ADJUSTABLE 60 to 100% OF INPUT VOLTAGE
ACCELERATION / DECELERATION ...................................... (MODEL 730BDC and 731BDC) FAST START
INTERNAL VOLTAGE SUPPLY (FOR MOTOR HALL SPACINGS) .................................................. +6.2 VDC
Heatsink & Cooling
F.), adding more heatsink or decreasing the current to keep the heatsink
o
C is a must. Finally, no matter what the heatsink temperature, never
o
Specifications
......................................... (733BDC) ADJUSTABLE 0 – 10 SECONDS
8
C. (167
F.). The control, as
o
o
OR 120
o
0
C. to 45
C. (32
F. to 113
o
o
o
o
F.)
o
Need help?
Do you have a question about the 730 Control Series and is the answer not in the manual?