Installation

WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could
result in death or serious injury. Disconnect all electric
power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
1. Remove the unit and packaging from the crate. Inspect
the unit. Carefully remove the stretch wrap and
cardboard pieces. The installation literature and may
be found on the back of the unit in a clear, plastic bag.
Unit has been tied to skid by (2) shipping brackets.
2. Remove refrigeration panel and inspect the unit. Be
certain the refrigerant tubing has clearance from
adjacent parts. Verify that the electrical connections
are tight and in-place.
Chassis Refrigeration
Front Panel
Shipping Brackets
3. With the chassis still on the subbase, align the unit to
the wall. If unit contains an outside air option, align the
wall cut-out to the subbase outside-air cut-out. Level
the unit per plan requirements. Mark the four
mounting locations for wall sleeve mounting to the
wall. The dimensions should fall in line with Step 5.
4. Remove the chassis from the subbase via 6 screws. The
chassis is attached to both the subbase and the wall
sleeve (see diagram above). To assure proper
20
alignment, re-install screws 2 and 3 in the final
installation of the unit (Step 11).
1
2
5. After removing chassis from the subbase, install the
wall flange assembly to the desired wall with the use of
four #10-field provided screws. The wall flange
assembly includes four,¼ in. diameter clearance holes.
6. Mounting of the receptacle box (option) should be
made prior to piping and electrical hook-up. This
factory disconnect option is designed to fit inside the
end pocket. Mount the receptacle box 2 in. above the
top of the subbase with four, #8-field supplied screws.
Mounting Locations
7. Mounting of the circuit breaker/receptacle box (option)
should be made prior to piping and electrical hook-up.
This factory disconnect option is designed to fit inside
the end pocket. Mount the electrical box flush with the
subbase with four, #8-field supplied screws.
8. Wiring of receptacle box (option). Power wiring to the
equipment should be installed per national and local
electric codes by a professional electrician. Power
wiring to the receptacle box may be done at this time.
See the unit's wiring schematic for field wiring.
5
6
47 1/4"
or
62 1/4"
RECEPTACLE BOX
(FACTORY OPTION)
#10 FIELD
(4)--#8 FIELD
PROVIDE
PROVIDED
MOUNTING
MOUNTING
DEVICE
DEVICE
SEE UNIT WIRE
DIAGRAM FOR
ELECTRICAL HOOK-UP
4
3
15 3/4"
2"
7 1/4"
WSHP-SVX11E-EN