Models 1507 and 1508
Output Voltage
(0 % to + 20 %)
100 V
(0 % to + 20 %)
250 V
(0 % to + 20 %)
500 V
(0 % to + 20 %)
1000 V
(0 % to + 20 %)
Model 1503
Output Voltage
500 V
(0 % to + 20 %)
1000 V
0 % to + 20 %)
EN61557 Specification (Models 1503 and 1507)
The following tables are a requirement for European labeling.
Volts
Earth-Bond Resistance
Insulation Resistance
[1]
This specification comes from the standard and indicates the maximum amount allowable by the standard.
EN61557 Influence Variables and Uncertainties (Models 1503 and 1507)
Earth-Bond Resistance
Influence Variable
Supply Voltage
Temperature
[1]
Specification confidence level 99 %.
Downloaded from
Elcodis.com
electronic components distributor
Display Range
0.01 to 20.00 MΩ
50 V
20.0 to 50.0 MΩ
0.01 to 20.00 MΩ
20.0 to 100.0 MΩ
0.01 to 20.00 MΩ
20.0 to 200.0 MΩ
0.01 to 20.00 MΩ
20.0 to 200.0 MΩ
200 to 500 MΩ
0.1 to 200.0 MΩ
200 to 2000 MΩ
2.0 to 10.0 GΩ
Display Range
0.01 to 20.00 MΩ
20.0 to 200.0 MΩ
200 to 500 MΩ
0.1 to 200.0 MΩ
200 to 2000 MΩ
Measurement
Designation per EN61557
Resolution
Test Current
0.01 MΩ
1 mA @ 50 kΩ
0.1 MΩ
0.01 MΩ
1 mA @ 100 kΩ
0.1 MΩ
0.01 MΩ
1 mA @ 250 kΩ
0.1 MΩ
0.01 MΩ
0.1 MΩ
1 mA @ 500 kΩ
1 MΩ
0.1 MΩ
1 mA @ 1 MΩ
1 MΩ
0.1 GΩ
Resolution
Test Current
0.01 MΩ
1 mA @ 500 kΩ
0.1 MΩ
1 MΩ
0.1 MΩ
1 mA @ 1 MΩ
1 MΩ
Intrinsic Uncertainty
± (2.0 % + 3)
± (1.5 % + 3)
Depends on test voltage and range.
See Insulation Test specifications.
Uncertainty for Insulation
Resistance
E2
5 %
E3
5 %
Insulation Testers
Electrical Specifications
Accuracy
± (% of Rdg + Digits)
± (3 % + 5)
± (3 % + 5)
± (1.5 % + 5)
± (1.5 % + 5)
± (1.5 % + 5)
± (10 % + 3)
Accuracy
± (% of Rdg + Digits)
± (2.0 % + 5)
± (2.0 % + 5)
1
Operating Uncertainty
30 %
30 %
30 %
Uncertainty for Earth-Bond
1
Resistance
1
5 %
5 %
5