Download Print this page

JUMO 902442 Installation Instructions Manual page 7

Screw connection for temperature probe installation in plastic or brass

Advertisement

Installation
In measuring point M10 x 1 according to EN 1434 (ball valve, T-piece, adapter screw fitting or heat meter
housing)
(1)
O-ring
(2)
Assembly aid
(3)
Temperature probe with screw connection
(4)
Measuring point according to EN 1434/M10 x 1
1. Place the O-ring onto the assembly aid.
2. Insert into the measuring point and remove the assembly aid.
3. Insert the temperature probe through the O-ring and into the measuring point and tighten the screw
connection, tightening torque 3 to 5 Nm (when installed correctly, the bottom of the hexagon sits on
top of the standard-compliant measuring point).
A new O-ring must be used after each dismounting process.
When mounted, the following applies for the adapter screw fitting set:
Max. operating temperature: 150 °C
Pressure stage: PN16
2 Installation specifications for direct mounting
(3)
(1)
(2)
(4)