8
TECHNICAL DATA
Supported PLCs
Weight in kg
Dimensions (W x H x D) in mm
MPI interface
Type:
Transmission rate:
Line:
Connection:
Modem connection
Type:
Connection:
Communication interface
Type:
Transmission rate:
Connection:
Power supply
External power supply possible
Power consumption
Protection type
Electromagnetic compatibility (EMC)
Transient emissions
interference resistance on signaling
lines
interference resistance ESD
HF-radiance fields
Grid-pound HF interferences
Climatic conditions
Temperature operating
Temperature storage/transport:
Relative humidity operating:
ACCON-MPI-Modem 56k
S7-300, S7-400
ca. 0,24
135 x 67 x 30
RS485, pot. separated
19,2 KBit/s or 187,5 KBit/s
1,2 m
9-pin SUB-D plug
RS232, serial asynchronous
RJ11 bushing
Analog modem connection
19,2 KBit/s to 115,2 KBit/s
Automatic detection!
9-pin SUB-D plug
24 VDC ± 25 %
Yes
Max. 100 mA
IP 30
Class B according to EN55022
±2kV according to EN61000-4-4
±6kV contact discharge method
EN61000-4-2
±8kV air discharge method
EN61000-4-2
10V/m according to EN61000-4-3
10V according to EN61000-4-6
0° C to 60° C
-20° C to 60° C
5 % to 85 % at 30° C (no bedewing)