Initial Commissioning Using Electronic Control Unit Whse - Helios WHS HE Installation And Operating Instructions Manual

Temperature control system
Table of Contents

Advertisement

Available languages

Available languages

Installation and Operating Instructions
EN
CHAPTER 3
COMMISSIONING
Temperature Control System WHS HE
3�1

Initial commissioning using electronic control unit WHSE

1. Check correct wiring.
2. If everything is attached correctly, connect the supply voltage and carry out the following tests for the respectively
correct temperature regulation.
– Function test
Sensor operating mode 1: Constant supply air temperature control
Sensor operating mode 1: Constant supply air temperature control
Setpoint setting
on WHSE
duct sensor Frost
protection
1. Set DIP switches (Pos.û) 2, 3 and 5 to Position A and DIP switches 1 and 4 to Position B.
2. Turn the internal setpoint potentiometer (Pos. â) clockwise to the end position.
LED Y1 (Pos. á) should light up and the actuator should open the three-way valve.
3. Turn the internal setpoint potentiometer (Pos. â) counter clockwise to the end position.
LED Y2 (Pos. é) should light up and the actuator should close the three-way valve.
â
ê
ô
Sensor operating mode 2: Constant room temperature control
Sensor operating mode 2: Constant room temperature control
Setpoint
1. Set DIP switches (Pos.û) 3 and 5 to Position A and DIP switches 1, 2 and 4 to Position B.
2. Turn the external setpoint potentiometer (TFR) clockwise to the end position.
LED Y1 (Pos. á) should light up and the actuator should open the three-way valve.
3. Turn the external setpoint potentiometer (TFR) counter clockwise to the end position.
LED Y2 (Pos. é) should light up and the actuator should close the three-way valve.
â
ê
ô
duct sensor
Main sensor
â Setpoint temperature for operation with constant supply air temperature
û
áé
ó
ú
ê CF = Cascade factor setting
ô MIN = Minimum limit
û Setting/selection of control mode via Dip switches
á Actuator operating display Y1
é Actuator operating display Y2
ó nti-freeze: LED alarm and reset button
ú Operating display
duct sensor
Frost protec-
tion
â Setpoint temperature for operation with constant supply air temperature
û
áé
ó
ú
ê CF = Cascade factor setting
ô MIN = Minimum limit
û Setting/selection of control mode via Dip switches
á Actuator operating display Y1
é Actuator operating display Y2
ó nti-freeze: LED alarm and reset button
ú Operating display
14
Fig� 18
.
Fig� 19
TFR room sensor
and setpoint
setting