5796 Expansion Unit - IBM 8202-E4B Manual

Hide thumbs Also See for 8202-E4B:
Table of Contents

Advertisement

Table 41. Service clearances for rack-mounted expansion unit
Front
914 mm (36 in.)
1
Side and top clearances are optional during operation.
Table 42. Service clearances for stand-alone expansion unit
Front
368.3 mm (14.5 in.)
Safety compliance: This hardware is designed and certified to meet the following safety standards: UL
60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all National Differences
Related information:
Acoustics

5796 expansion unit

Hardware specifications provide detailed information for your expansion unit, including dimensions,
electrical, power, temperature, environment, and service clearances.
Table 43. Dimensions I/O drawer only
Height
172 mm (6.8 in.)
Table 44. Dimensions - with required I/O drawer mounting enclosure
Height
176 mm (6.9 in.)
Table 45. Maximum configuration weight
One I/O drawer
20 kg (44 lb)
Table 46. Electrical
Electrical characteristics
kVA
Rated voltage and frequency
Thermal output
Power requirements (maximum)
Power factor
Table 47. Temperature requirements
Operating
10°C - 38°C (50°F - 100°F)
The upper limit of the dry-bulb temperature must be derated 1°C per 137 m (450 ft) above 915 m (3000 ft).
26
Site and hardware planning
Back
914 mm (36 in.)
Back
381 mm (15 in.)
Width
224 mm (8.8 in.)
Width
473 mm (18.6 in.)
Two I/O drawers plus the mounting enclosure
45.9 kg (101 lb)
Properties
0.275
200 - 240 V ac at 50 - 60 Hz, V dc not supported
853 Btu/hr
250 W
0.91
Nonoperating
1°C - 60°C (33.8°F - 140°F)
1
Sides
914 mm (36 in.)
Depth
800 mm (31.5 in.)
Depth
800 mm (31.5 in.)
Storage
1°C - 60°C (33.8°F - 140°F)

Advertisement