Table 153. 7189 PDU+ specifications
Characteristics
PDU number
Height
Width
Depth
Additional clearance
Weight (not including power cord)
Weight of power cord (approximate)
Operating temperature at 0 - 914 m (0 - 3000 ft)
(room ambient)
Operating temperature at 914 - 2133 m (3000 -
7000 ft) (room ambient)
Operating humidity
Localized air temperature in PDU
Rated frequency (all feature codes)
Circuit breakers
Power outlet
7196 PDU+
Table 154. 7196 PDU+ features
PDU Number
Racks usage
7196 PDU+
7014-B42
Table 155. 7196 PDU+ specifications
Characteristics
PDU number
Height
Width
Depth
Additional clearance
Weight (not including power cord)
Weight of power cord (approximate)
Operating temperature at 0 - 914 m (0 - 3000 ft)
(room ambient)
Operating temperature at 914 - 2133 m (3000 -
7000 ft) (room ambient)
Operating humidity
Localized air temperature in PDU
Rated frequency (all feature codes)
Circuit breakers
Properties
7189
43.9 mm (1.73 in.)
447 mm (17.6 in.)
350 mm (13.78 in.)
25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets
6.3 kg (13.8 lb)
5.4 kg (11.8 lb)
10 - 32°C (50 - 90°F)
10 - 35°C (50 - 95°F)
8 - 80% (noncondensing)
60°C (140°F) maximum
50 - 60 Hz
Six double-pole branch rated circuit breakers rated at 20 A
Six IEC 320-C19 outlets rated at 16 A (VDE) or 20 A (UL/CSA)
Supported power cords PDU to wall
Fixed power cord with IEC 60309, 3P+E, 60 A plug
Properties
7196
43.9 mm (1.73 in.)
447 mm (17.6 in.)
350 mm (13.78 in.)
25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets
6.3 kg (13.8 lb)
5.4 kg (11.8 lb)
10 - 32°C (50 - 90°F)
10 - 35°C (50 - 95°F)
8 - 80% (noncondensing)
60 °C (140 °F) maximum
50 - 60 Hz
Six double-pole branch rated circuit breakers rated at 20 A