Lilytech ZL-R200A Instruction Manual

Lilytech ZL-R200A Instruction Manual

Heat pump water heater controller

Advertisement

Quick Links

ZL-R200A Heat Pump Water Heater Controller
Main Function
Auxiliary heating function
Water flowing warning
Ventilation pump control
Antifreeze function
Sensor failures action
Technical Specification
Sensor:
NTC 10K/3470
Set range:
20
60℃
~
Display range:
-40
130℃
~
Working temperature:
0
50℃
~
Storage temperature:
-10
60℃
~
Ambient humidity:
20
85%RH without dew
~
Power supply:
220Vac ± 10% 50/60Hz
Load:
Compressor 15A
Heating 8A
Others 3A
Failure Code
No.
Code
1
E01
Water container sensor failure
2
E02
Pipe Coil sensor failure
3
E03
Exhaustion sensor failure
4
E04
Outdoor sensor failure
Display Indication
Icon
Display
Online
Heating
Electrical heating
Outdoor fan running
Defrosting
Key Operation
Temperature Inquiry
Press
key to check all sensors' temperature consecutively. The result keeps displaying for 3 seconds.
Instruction Manual
Failure
Not shown
Offline
Not heating
Electrical heater off
Outdoor fan stop
Not defrosting now
Page 1, Total 4 Pages
V1.0c
Auto defrost function
Auto restart function
Exhaustion temperature protection
Compressor delay and pressure protection
No.
Code
5
E05
Water flow warning
6
E06
High/low pressure input warning
7
E07
Data saving failure
8
E08
Communication failure
Icon
Displaying
Compressor running Compressor stop
Pump running
Four valves on
Locked
Suzhou Lily Tech. Co., Ltd.
Failure
Not shown
Pump stop
Four valves off
Unlocked

Advertisement

loading
Need help?

Need help?

Do you have a question about the ZL-R200A and is the answer not in the manual?

Questions and answers

Summary of Contents for Lilytech ZL-R200A

  • Page 1 Suzhou Lily Tech. Co., Ltd. ZL-R200A Heat Pump Water Heater Controller Instruction Manual V1.0c Main Function Auxiliary heating function Auto defrost function Water flowing warning Auto restart function Ventilation pump control Exhaustion temperature protection Antifreeze function Compressor delay and pressure protection...
  • Page 2 Suzhou Lily Tech. Co., Ltd. On/Off Keep key depressed for 3 seconds to switch between online and offline. Set (water) Temperature (SP) Press key to set temperature. Keep depressed can fast set. Factory default set is 40℃. System Parameter Set depressed for 3 seconds, the big digits show “P00”...
  • Page 3 Suzhou Lily Tech. Co., Ltd. Control Function Temperature Control When T-water ≤ SP – U01, start heating. When T-water ≥ SP, stop heating. Heating start procedure: Pump is on; 30 seconds later, outdoor fan is on, valve takes action; 30 seconds later, compressor is on. Heating stop procedure: Compress is off;...
  • Page 4 Suzhou Lily Tech. Co., Ltd. Wiring Diagram Attention Set U34 correctly, otherwise system does not work correctly. The real clock can only keep running correctly for 72 hours after power supply loses. All sensors must be installed at correct position. Do not plug in/out panel bundle with power supplied.