Page 1
Suzhou Lily Tech. Co., Ltd. ZL-R200A Heat Pump Water Heater Controller Instruction Manual V1.0c Main Function Auxiliary heating function Auto defrost function Water flowing warning Auto restart function Ventilation pump control Exhaustion temperature protection Antifreeze function Compressor delay and pressure protection...
Page 2
Suzhou Lily Tech. Co., Ltd. On/Off Keep key depressed for 3 seconds to switch between online and offline. Set (water) Temperature (SP) Press key to set temperature. Keep depressed can fast set. Factory default set is 40℃. System Parameter Set depressed for 3 seconds, the big digits show “P00”...
Page 3
Suzhou Lily Tech. Co., Ltd. Control Function Temperature Control When T-water ≤ SP – U01, start heating. When T-water ≥ SP, stop heating. Heating start procedure: Pump is on; 30 seconds later, outdoor fan is on, valve takes action; 30 seconds later, compressor is on. Heating stop procedure: Compress is off;...
Page 4
Suzhou Lily Tech. Co., Ltd. Wiring Diagram Attention Set U34 correctly, otherwise system does not work correctly. The real clock can only keep running correctly for 72 hours after power supply loses. All sensors must be installed at correct position. Do not plug in/out panel bundle with power supplied.