Specifications

Allowable operating voltage range
Allowable operating frequency range
Input frequency range
Overload capacity
Operating value
Repeat error
Operating time
Conforming standards
Applicable stan-
EMC
dards
Safety standards
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Degree of protection
85% to 110% of rated power supply voltage
50/60 Hz ±5 Hz
40 to 500 Hz
Continuous input at 115% of maximum input, 10 s at 125% (up to 600 VAC).
±0.5% full scale (at 25°C and an ambient humidity of 65% at the rated power supply voltage, DC and 50/60
Hz sine wave input)
±50 ms (at 25°C and 65% humidity, rated power supply voltage)
EN60947-5-1
Installation environment (pollution level 2, installation category III)
EN60947-5-1
UL 508 (Recognition), Korean Radio Waves Act (Act 10564),
CSA: CAN/CSA C22.2 No.14, CCC: GB14048.5
20 MΩ min.
Between all external terminals and the case
Between all power supply terminals and all input terminals
Between all power supply terminals and all output terminals
Between all input terminals and all output terminals
2,000 VAC for 1 min
Between all external terminals and the case
Between all power supply terminals and all input terminals
Between all power supply terminals and all output terminals
Between all input terminals and all output terminals
1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 μs/100 ns pulse width with 1-ns rise time
Frequency: 10 to 55 Hz, acceleration 50 m/s
10 sweeps of 5 min each in X,Y, and Z directions
150 m/s
2
3 times each in 6 directions along 3 axes. Or 100 m/s
Terminals: IP20
2
2
for relay contacts.
K8AK-VW