TABLE 6-1. SALE AND UNIT PRICE DISPLAYS ARE BLANK.

Probable Cause
1.
No power to computer.
2.
Defective display.
3.
Defective computer.

TABLE 6-2. DISPLAY SEGMENTS FAIL TO OPERATE DURING RESET CYCLE

Probable Cause
1.
Defective display assembly.
2.
Defective data cable.
3.
Defective computer.
A. For other detailed information about faulty displays, see Figure A-20.
Probable Cause
1.
Control system unit price set at 0.000.
2.
Unit price not set at dispenser. If a control
system is connected go to Step 4.
3.
Data was corrupted then cleared by the
computer. Check option 01 to verify. See
programming manual part number
920205 for details.
4.
Fueling point # not set. If a control system
is not connected go to Step 5.
5.
Defective computer.
42
Part No. 920160 Rev A
Corrective Action
Check control power circuit breaker
Check for AC between pins 1 and 2 of J3 connector. If not
present check in J-box. If not present in J-box problem is in
site wiring. If 110 VAC is present in the J-box the problem is
in the dispenser internal wiring.
Check F1 and F3 on computer board and replace as necessary.
Replace the display board.
Replace.
Corrective Action
Replace the faulty display assembly.
Replace data cable.
Replace computer assembly.

TABLE 6-3. UNIT PRICE DISPLAYING 0.000.

Corrective Action
Set correct unit price in control system. Refer to the control
system operation manual.
Set correct price using price jog switch.
Reset prices and or option programming. If problem contin-
ues to occur replace computer assembly.
Set fueling point.
Replace computer assembly.