01 06 00 01 00 01 19 CA(ModbusT RTU) ;
Note: In the Modbus TCP standard protocol, the thing element identifier is specified, and in E842-DTU(EC03-485), the user
can configure the value through the AT-MTCPID, and when the value is configured to 0, the receiving end resolves and converts
all Modbus TCP-compliant data, otherwise only the packet identifier applied will be converted with the same identifier as the
device configuration.
4.5 Serial packaging feature
E842-DTU (EC03-485) serial frame break time and packaging length can be configured, and the user can configure frame
break time and package length through parameter configuration software.
Frame break time: When the frame break time receives data for a serial port, the interval between two bytes of phase
collar is constantly detected, and if it is greater than the user's configured time (which can be set to 50-2000ms),the device
automatically sends the previously received data as a packet to the network side;
Package length: When packaging the length of the serial to receive data, the currently received data length is constantly
checked, if the length of the user configuration (can be set to 20 to 1024 bytes), the device will automatically receive the
previously received data as a packet to the network side;
4.6 Network AT functionality
E842-DTU (EC03-485)) supports networking on the connection, and the module works in transmission mode after sending
commands in the following format via connected web pages, remote queries/configuration parameters
< Head > AT-CMD, where the < Head > is the device network AT identifier, which is factory default:EbyteNET, and CMD is
the corresponding command