Installing the Zoneline
10. Make electrical connections to unit
ELECTRICAL CONNECTIONS - DIRECT CONNECT
WARNING
Before servicing, disconnect power to the Zoneline at
the fuse box or circuit breaker and pull out electrical
disconnect on front of the chassis.
Failure to do so can result in personal injury and/or
death.
208/230/265 Volt Electrical Supply
A power supply kit must be used to supply power to
the Zoneline unit. The appropriate kit is determined
by the voltage, the means of electrical connection and
the amperage of the branch circuit. See the POWER
CONNECTION CHART to select the appropriate kit.
Power Supply Kit - Direct Connect
FOR 265 VOLT DIRECT CONNECT
APPLICATIONS ONLY
IMPORTANT: Connection of a 265V AC product to a
branch circuit MUST be done by direct connection in
accordance with the National Electrical Code. Plugging
this unit into a building mounted exposed receptacle is
not permitted by code.
These models must be installed using the appropriate
GE Appliances power supply kit for the branch circuit
amperage and the electrical resistance heater wattage
desired. See the POWER CONNECTION CHART to
select the appropriate kit.
It is the responsibility of the installer to ensure the
connection of components is done in accordance with
electrical codes.
Direct connection to branch circuit wiring inside the
provided junction box must be made by connecting as
follows in steps 1–3.
22
APPLICATIONS
Electric Shock Hazard
EXTERNAL DISCONNECT
There shall be disconnecting means from the electrical
supply located within line of sight of the closet door
opening or access panel opening. The disconnecting
means shall be readily accessible while the air
conditioner is installed in the closet. The disconnect
shall not obscure the rating plate or be located on the
access panel or closet door. A properly rated switch is
a common means for electrical disconnection.
1. Remove Junction Box Cover
Remove the junction box cover by taking out the
three screws.
2. Attach Conduit
Use the round knockout hole at the top of the
junction box to install conduit coming from the
branch circuit. Install and clamp the conduit through
the conduit clamp and bring wire leads into the
junction box. Leave 8" of wire free from the end of
the conduit.
8" of wire free