Check programmes – Overview
A
Prüfprogramme
P.00 Purging
P.01 Maximum load
P.02 Minimum load
P.05 ST test
Function menu – Overview
B
Display
Activating the function menu
Check heating pump?
Check fan?
Check charging pump?
Check circ. pump?
Check external pump?
Purge hydraulics?
Test burner?
End function menu?
26
Meaning
Purge the product, heating circuit and cylinder charging circuit. The product does not start up. The
heating pump runs intermittently. After approx. 6.5 minutes, the product switches to the cylinder char-
ging pump (alternatively, by pressing the i button).
Start up the burner at maximum load. The product works at maximum load after a successful ignition.
Start up the burner at minimum load. The product works at minimum load after a successful ignition.
Test function for the safety cut-out (SCO): The burner is switched on at maximum power and the
pumps are switched off; the temperature control is switched off so that the burner heats up until the
safety cut-out is triggered by reaching the safety cut-out temperature.
Action
Result
→ + button: Yes
Function menu activated
→ − button: No
End, normal operating mode starts
→ i button: Yes
Pump test started
+ button: Next
− button: Back
→ i button: Yes
Fan is actuated at max. rotational speed.
+ button: Next
− button: Back
→ i button: Yes
All connections that are defined as the
cylinder charging pump receive mains
+ button: Next
voltage.
− button: Back
- 2 in 7 module if D.27 or D.28 = 3
→ i button: Yes
All connections that are defined as the
circulation pump receive mains voltage.
+ button: Next
- PCB if D.26 = 1
− button: Back
- 2 in 7 module if D.27 or D.28 = 1
→ i button: Yes
All connections that are defined as the
external pump receive mains voltage.
+ button: Next
- 2 in 7 module if D.27 or D.28 = 2
− button: Back
→ i button: Yes
Water pressure is displayed.
+ button: Next
− button: Back
→ i button: Yes
The heating pump is actuated at the
same time as the burner
+ button: Next
Flow target temperature = maximum flow
− button: Back
temperature target value
→ i button: Yes
Normal operating mode starts
+ button: Next
Restart the function menu
− button: Back
Back
Installation and maintenance instructions ecoVIT exclusiv 0020258610_00
Option
+ button: Pump on
− button: Pump off
→ i button: Back
+ button: Fan on
− button: Fan off
→ i button: Back
+ button: Cylinder charging pump
on
− button: Cylinder charging pump
off
→ i button: Back
+ button: Circulation pump on
− button: Circulation pump off
→ i button: Back
+ button: External pump on
− button: External pump off
→ i button: Back
+ button: DHW circuit
− button: Heating circuit
→ i button: Back
+ button: Burner on
− button: Burner off, function
menu ends