Errors & Input Settings
This page defines how the individual relays will react to time outs and errors present from any defined T24
device, as well as how Digital inputs 1 and 2 are used.
Items you can change:
Timeout
Error Action
Error Mode
Digital Input 1
Digital Input 2
Mantracourt Electronics Limited T24-RM1 User Manual
Enter a time in seconds that if exceeded the T24-RM1 will affect the relay state
according to the error action, as well as set the alarm relay and light the time
out LED
For each relay the action upon error detection can be defined as ;
Hold Last State
De-Energise Relay
Energise Relay
The error mode defines what is causes the alarm relay and individual error
action to be triggered. Errors can be defined as
Time out
Time out or Low Battery
Time out or Low Battery or Integrity Error
Digital input 1 can be used to either
Reset Relay 1 from its latched state
Transmit a data provider with user defined data tag containing the total
of the inputs of Relay 1
Digital input 2 can be used to either
Reset Relay 2 from its latched state
Transmit a data provider with user defined data tag containing the total
of the inputs of Relay 2
16