1. Single phase unit
Nameplate
maximum
current
No more than 10A
10~16 A
16~25 A
25~32 A
32~40 A
40 ~63 A
63~75 A
75~101 A
101~123 A
123~148 A
148~186 A
186~224 A
2. Three phase unit
Nameplate
maximum
current
No more than 10A
10~16 A
16~25 A
25~32 A
32~40 A
40 ~63 A
63~75 A
75~101 A
101~123 A
123~148 A
148~186 A
186~224 A
When the unit will be installed at outdoor, please use the cable which can against UV.
27
Phase line
Earth line
2×1,5 mm
2
1,5 mm
2
2×2,5 mm
2,5 mm
2
2×4 mm
4 mm
2
2×6 mm
6 mm
2
2×10 mm
10 mm
2
2×16 mm
16 mm
2×25 mm
2
25 mm
2×25 mm
2
25 mm
2
2×35 mm
35 mm
2
2×50 mm
50 mm
2
2×70 mm
70 mm
2
2×95 mm
95 mm
Phase line
Earth line
2
3×1,5 mm
1,5 mm
2
3×2,5 mm
2,5 mm
3×4 mm
2
4 mm
3×6 mm
2
6 mm
2
3×10 mm
10 mm
2
3×16 mm
16 mm
2
3×25 mm
25 mm
2
3×25 mm
25 mm
2
3×35 mm
35 mm
3×50 mm
2
50 mm
3×70 mm
2
70 mm
2
3×95 mm
95 mm
MCB
Creepage protector
2
20 A
30mA less than 0.1 sec
2
32 A
30mA less than 0.1 sec
2
40 A
30mA less than 0.1 sec
2
40 A
30mA less than 0.1 sec
2
63 A
30mA less than 0.1 sec
2
30mA less than 0.1 sec
80 A
2
100 A
30mA less than 0.1 sec
2
125 A
30mA less than 0.1 sec
2
160 A
30mA less than 0.1 sec
2
225 A
30mA less than 0.1 sec
2
250 A
30mA less than 0.1 sec
2
280 A
30mA less than 0.1 sec
MCB
Creepage protector
2
20 A
30mA less than 0.1 sec
2
32 A
30mA less than 0.1 sec
2
40 A
30mA less than 0.1 sec
2
40 A
30mA less than 0.1 sec
2
63 A
30mA less than 0.1 sec
2
80 A
30mA less than 0.1 sec
2
100 A
30mA less than 0.1 sec
2
125 A
30mA less than 0.1 sec
2
160 A
30mA less than 0.1 sec
2
225 A
30mA less than 0.1 sec
2
250 A
30mA less than 0.1 sec
2
280 A
30mA less than 0.1 sec
Signal line
2
n×0.5mm
Signal line
n×0.5mm
2