Fault Codes Indicated By Led's On The Cooler Electronics Module - Seeley CW-6S Installation Manual

Microcore indirect evaporative cooler
Hide thumbs Also See for CW-6S:
Table of Contents

Advertisement

FAULT CODES INDICATED BY LED's ON
THE COOLER ELECTRONICS MODULE
The CW3 cooler has 2 LED's visible on the control PCBA. One
is Tri-Colour and can glow Green, Red or Amber.
The other is Red only.
TRI-COLOUR LED
Wall Control
LED
Fault Code
2 Green Flash then
-
2 seconds off
1 Red Flash then 2
Fault Code #1
seconds off
2 Red Flash then 2
Fault Code #2
seconds off
3 Red Flash then 2
Fault Code #3
seconds off
4 Red Flash then 2
Fault Code #4
seconds off
5 Red Flash then 2
Fault Code #5
seconds off
6 Red Flash then 2
Fault Code #6
seconds off
7 Red Flash then 2
Fault Code #7
seconds off
-
Fault Code #8
1 Green/Red Flash
then 2 seconds off
2 Green/Red Flash
then 2 seconds off
3 Green/Red Flash
then 2 seconds off
Fault Code #10
+ 10 Red Flash
4 Green/Red Flash
then 2 seconds off
5 Green/Red Flash
then 2 seconds off
Fault Code #10
+ 10 Red Flash
13 Red Flash
Fault Code #13
RED COLOURED LED: This LED indicates the status of the
conductivity measurement circuit and the status of the Salinity
Control Method
RED LED
LED
Fault Description
On Solid
No Water at Low Probe or Conductivity <9μS/cm
1 Red Flash
Water Manager and Conductivity < 1500μS/cm
2 Red Flash
Water Manager and Conductivity < MAX (Parameter A5).
3 Red Flash
Count 8 re-fills to High Probe (Parameter A1)
4 Red Flash
24 Hour Clean Drain Mode Running
26 |
Fault Description
NORMAL OPERATION
COMMUNICATION FAILURE
Wall Control: No valid message for 60 seconds
FAILURE TO DETECT WATER AT LOW PROBE
No water at low probe 20 minutes after solenoid valve opening.
FAILURE TO DETECT WATER AT HIGH PROBE
No water at high probe 10 minutes after water detected at low
probe.
FAILURE TO CLEAR LOW PROBE DURING DRAIN
Water still detected at low probe 5 minutes after drain opened.
WATER DETECTED AT HIGH PROBE BUT NOT LOW PROBE.
FAILURE TO CLEAR HIGH PROBE.
Water still detected at high probe after Pump Test sequence.
SUPPLY MOTOR ERROR.
WARM START
Mains input voltage is under 93Vac but not low enough to reset
the PCB. Fault Code recorded when voltage returns to useable
level.
CHLORINATOR PERFORMANCE DEGRADED
Chlorinator operating current is less than set point.
CHLORINATOR PERFORMANCE SERIOUSLY DEGRADED
Chlorinator operating current is less than 50% of set point.
CHLORINATOR REACHED END OF LIFE
CHLORINATOR SHORT CIRCUIT WARNING
Chlorinator current >> target.
CHLORINATOR SHORT CIRCUIT FAULT
Chlorinator current >> target again within 15 mins of reservoir
drain and re-fill.
EXHAUST MOTOR ERROR.
Suggested Remedy
-
Check communication cable connections.
Replace Wall Control.
Replace Communication Cable.
Check water supply on.
Check solenoid valve open.
Check drain valve closed.
Check water management probe position relative to drain
valve overflow.
Clean water management probe.
Check solenoid valve open.
Check water management probe position relative to drain
valve overflow.
Clean water management probe.
Check water supply pressure sufficient to maintain tank
capacity.
Check drain valve open.
Check drain pipework not blocked.
Check solenoid valve closed.
Clean water management probe.
Clean water management probe.
Check solenoid valve not stuck open.
Check all pumps operating when required
Clean pumps.
Check pump hoses not blocked.
Check excessive rain not entering cooler.
Clean water management probe.
Check Motor Power Cable connections.
Check Motor Communications Cable connections
Consult with Building Manager.
Clean Chlorinator
Check flushing hose correctly attached.
Prepare to replace Chlorinator at next service.
Replace Chlorinator now to avoid fault in near future.
Replace Chlorinator now.
Clean Chlorinator
Check flushing hose correctly attached.
Check no debris between the Chlorinator Plates.
Check no debris between the Chlorinator Plates.
Replace Chlorinator now.
Check Motor Power Cable connections.
Check Motor Communications Cable connections
TRI-COLOUR LED
RED LED
ILL2465-A

Advertisement

Table of Contents
loading