Product Line - Infinite Transtector DCPDU2B Series Installation Manual

Table of Contents

Advertisement

3.0

PRODUCT LINE

3.1
Configurations
The following table lists the 5 available configurations of the DCPDU2B series.
3.2
Available Breakers
+1 (208) 635-6400 | www.transtector.com
STANDARD DUAL FEED CONFIGURATIONS
MODEL
NUMBER
DCPDU2B-D-2X10-450
OPTIONAL SINGLE FEED CONFIGURATIONS
MODEL
NUMBER
DCPDU2B-S-X20-450
1
AMPS
PART NUMBER
2.5
DCBKR2B-2.5
5
DCBKR2B-5
10
DCBKR2B-10
15
DCBKR2B-15
20
DCBKR2B-20
25
DCBKR2B-25
30
DCBKR2B-30
40
DCBKR2B-40
NOTES:
1. Breakers need to be ordered individually and are shipped separately.
2. Require two positions. Includes paralleling bars to connect output load terminals.
3. Breakers are magnetic-hydraulic plug-in type with auxiliary contacts (Normally Open) and mid-trip
function. Only the following types may be installed.
2.5A to 100A:
CBI D-Frame Series single pole, D-2A23XANBSXXXXLXB-XXXXXWDVAX2-X
or
Carling C-Series Handle single pole, CT1-B2-14-XXX-A11-MJ
125A to 200A:
CBI D-Frame Series, parallel pole, D-2A23XBNBSXXXXLAM-XXXXXWDVAX3-X
or
Carling C-Series Handle Parallel pole, CT2-P2-04-XXX-A11-MK
VOLTS
INPUT
EACH FEED
FEEDS
BREAKERS
48/24 - 48/24
2
VOLTS
INPUT
EACH FEED
FEEDS
BREAKERS
48/24
1
AMPS
PART NUMBER
50
DCBKR2B-50
60
DCBKR2B-60
80
DCBKR2B-80
100
DCBKR2B-100
125
DCBKR2B-125
2
150
DCBKR2B-150
2
200
DCBKR2B-200
2
MAX. #
AMPS
EACH FEED
10 A side
&
450
10 B side
MAX. #
AMPS
EACH FEED
20
450
TOTAL
AMPS
900
TOTAL
AMPS
450