DCPDU2B Series Power Distribution Units
Installation Manual
© 2021 Infinite Electronics, Inc. Transtector is a registered trademark of Infinite Electronics, Inc. | DCPDU2B-M Rev. 1

Advertisement

Table of Contents
loading

Summary of Contents for Infinite Transtector DCPDU2B Series

  • Page 1 DCPDU2B Series Power Distribution Units Installation Manual © 2021 Infinite Electronics, Inc. Transtector is a registered trademark of Infinite Electronics, Inc. | DCPDU2B-M Rev. 1...
  • Page 2: Table Of Contents

    Installation Manual | DCPDU2B Series Power Distribution Units DESCRIPTION CHK’d & APPR’d / DATE Production Release DR / 01-29-21 Contents INTRODUCTION .......................4 FEATURES ........................4 PRODUCT LINE ........................5 SAFETY & INDUSTRY STANDARDS ................6 WARRANTY (summary) ....................6 DESCRIPTION OF OPERATION ..................7 SPECIFICATIONS ......................8 FRONT PANEL DESCRIPTION ..................8 BACK PANEL DESCRIPTION ...................9 10.0...
  • Page 3 FIGURES Figure 1. DCPDU2B DC Power Distribution Panel ................4 Figure 2. Block Diagram ........................7 Figure 3. Front Panel View ......................8 Figure 4. Back Panel View ......................9 Figure 5. Input Bus Bar Detail ......................9 Figure 6. Output Barrier Strip Detail ....................10 Figure 7.
  • Page 4: Introduction

    Installation Manual | DCPDU2B Series Power Distribution Units OPERATING MANUAL DCPDU2B SERIES DC POWER DISTRIBUTION PANELS INTRODUCTION DCPDU2B Series circuit breaker panels provide distribution and overload protection for 1 to 20 circuits with circuit breakers that can be field installed/exchanged using a supplied puller tool. The panels are only two mounting positions (3.5 inches) high.
  • Page 5: Product Line

    PRODUCT LINE 3.1 Configurations The following table lists the 5 available configurations of the DCPDU2B series. STANDARD DUAL FEED CONFIGURATIONS MODEL VOLTS INPUT MAX. # AMPS TOTAL NUMBER EACH FEED FEEDS BREAKERS EACH FEED AMPS 10 A side DCPDU2B-D-2X10-450 48/24 - 48/24 &...
  • Page 6: Safety & Industry Standards

    Installation Manual | DCPDU2B Series Power Distribution Units SAFETY & INDUSTRY STANDARDS DCPDU2B Series power distribution panels meet the following safety requirements: STANDARD UL60950-1, 2nd Edition CSA22.2 No. 60950-1, 2nd Edition EN60950-1, 2nd Edition DCPDU2B Series power distribution panels are CE marked to indicate conformance to the European Union’s Low Voltage Directive.
  • Page 7: Description Of Operation

    DESCRIPTION OF OPERATION Power Distribution Circuits. A simplified schematic diagram of the distribution panels is shown in Figure 2. The battery input to each load connects to a high-current copper bus bar from which the individual fuses or circuit breakers distribute power to the loads.
  • Page 8: Specifications

    Installation Manual | DCPDU2B Series Power Distribution Units OUTLINE OF SAFETY COVER (blue dotted line) 4.60 SPECIFICATIONS (116.8) 0.76 1.13 (19.3) (28.7) The following specifications are typical at 25°C unless otherwise noted. 0.21 0.22 0.25 (5.3) (5.6) 0.42 (6.4) 0.56 0.37 (10.7) (14.2)
  • Page 9: Back Panel Description

    0.49 (12.5) x 0.31 (7.9) slot 3.50 0.90 (88.9) (22.9) 1.725 1.25 (43.82) (31.8) 0.500 0.625 (15.88) (12.70) is GND BACK PANEL DESCRIPTION READ) 0.57 (14.5) 0.750 Back View. Figure 4 shows the back of the DCPDU2B distribution panel. Inputs are (19.05) at the left and right ends of the back panel.
  • Page 10: Figure 6. Output Barrier Strip Detail

    OUTLINE OF SAFETY CO (blue dotted line) Installation Manual | DCPDU2B Series Power Distribution Units 4.60 (116.8) 0.76 1.13 Recommended Input Cable Sizes and Lugs (19.3) (28.7) 0.21 0.22 0.25 (5.3) (5.6) 0.42 (6.4) 0.56 0.37 (10.7) (14.2) (9.4) ø 0.306 (7.8) The following table details the recommended cable size for various input current.
  • Page 11: Figure 7. Alarm Connection Detail

    MAXIMUM CONDUCTOR PANDUIT CORP. TORQUE CURRENT SIZE PART NUMBER 1/4 x 20 BOLT 200A (2 pos) 3/0 AWG LCDX3/0-14A-X 62 in-lbs 150A (2 pos) 1/0 AWG LCDX1/0-14A-X 62 in-lbs 125A (2 pos) 1 AWG LCDX1-14A-X 62 in-lbs 100A (1 pos) 2 AWG LCDXN2-14A-E 62 in-lbs...
  • Page 12: Figure 9. Chassis Ground Connection

    0.76 1.13 (19.3) (28.7) 0.25 0.21 0.22 (5.3) (5.6) 0.42 (6.4) 0.56 0.37 Installation Manual | DCPDU2B Series Power Distribution Units (10.7) ø (14.2) (9.4) 0.306 (7.8) 0.49 (12.5) x Chassis Ground Connection. This is located on the left side of the chassis as shown 0.31 (7.9) slot in figure 9 below and is a pair of 1/4-20 bolts.
  • Page 13: Unpacking And Inspection

    10.0 UNPACKING AND INSPECTION 10.1 This DCPDU2B Series power distribution panel was carefully tested, inspected and packaged for shipment from our factory. The unit and circuit breakers are shipped separately. Upon receipt of the unit it should be carefully unpacked and inspected for any damage in shipment.
  • Page 14: 11.0 Installation

    Installation Manual | DCPDU2B Series Power Distribution Units 11.0 INSTALLATION 11.1 Mounting. This distribution panel can be mounted in either 19- or 23-inch racks by using the supplied reversible brackets. Mount it from the front of the rack using the correct offsets to align with existing rack-mounted equipment.
  • Page 15 The Form C relay contact output connections are made to the spring clamp terminal blocks. See Section 9.5. The chassis ground connection is made to the 1/4-20 studs. See Section 9.6. This safety ground connection should be made before operating the panel.
  • Page 16 Installation Manual | DCPDU2B Series Power Distribution Units 12.0 INSTALLING CIRCUIT BREAKERS The DCPDU2B Series employs pluggable circuit breakers that can be easily installed, removed or replaced using the supplied puller tools. This operation is carried out without the need to dismount the unit from it’s installation.
  • Page 17 The above table is based on the following: 1) Use of Carling (C Series) breakers or CBI (D Frame) breakers. Breakers in these series are equivalent in fit, form, and function and can be used interchangeably within the same system. 2) The DCPDU2B panel is rated for continuous operation at a maximum input of 450A per side @ 35C max., 400A per side @ 40C max., 320A per side @ 50C max., and 200A per side @ 70C max.
  • Page 18: 13.0 Setup And Testing

    Installation Manual | DCPDU2B Series Power Distribution Units 13.0 SETUP AND TESTING 13.1 It is not necessary to have the distribution panel mounted in a rack for initial testing. This can be done on a bench. It is also not necessary to have loads connected to the panel for this testing.
  • Page 19 Contact us at +1 208 635 6400 or online at www.transtector.com. About Infinite Electronics: Infinite Electronics is a leading global supplier of electronic components serving the urgent needs of engineers through a family of highly recognized and trusted brands. Our portfolio brands are specialists within their respective product set, offering broad inventories of engineering-grade product, paired with expert technical support and same day shipping.