REVISIONS REV. DESCRIPTION DATE APPROVED DOCUMENT RELEASE DD2922 3/7/2011 LS Plus 200 with LS Plus 200 Disconnect Switch DRAWN DATE 10701 Airport Drive, Hayden, ID 83835, USA ALL DIMENSIONS IN INCHES 2/21/11 UNLESS OTHERWISE SPECIFIED. +1.208.772.8515 FAX +1.208.762.6117 CHECKED 4/6/11 800.882.9110 www.protectiongroup.com TOLERANCES: ENG APPD...
Page 3
Pre-Install Notes READ ALL WARNINGS BEFORE ANY SERVICE OR TESTING Do not install, make any adjustments, or replace any components inside the enclosure with the power supply turned on. Under certain circumstances, dangerous potentials may exist even when the power supply is off. To avoid casualties, always turn the main power supply off before performing maintenance and/or testing.
Installation Procedure Notes Please read the entire installation manual before installing this SPD. Carefully unpack the SPD, removing all packaging material. Inspect for any signs of damage that may have occurred during shipment. If any damage is found, stop installation and contact LEA International.
AC Power Connection The SPD is installed in parallel with the incoming phase conductors. It is recommended to connect the SPD to a 60A circuit breaker. This allows for servicing of the SPD without shutting power off at the panel main breaker. Route all SPD conductors taking care to avoiding sharp bends and keeping all leads as short as possible, not exceeding five feet (5’).
Troubleshooting The SPD operational status can be seen on the front door of the enclosure. There is no need to open the unit for any reason. TVSS Status LED A green LED indicates power is applied and all SPD protection modes are normal. A red LED indicates the SPD needs servicing.
Page 7
Please Note: LS Plus 200 shown without the Disconnect Switch. The Operation of the Surge Counter and Audible Alarm Switch is same for both models. Alarm Disabled A Red Illuminated Light Indicates Audible Alarm is Disabled Surge Counter Records any Suppressed Transients Counter Reset Press to reset...
Page 8
179 mm 7-1/16" 508 mm 586 mm 20" 23-1/16" 152 mm 406 mm 6" 16" Use 3/8" [ 10 mm ] Mounting Hardware 548 mm 21-9/16" 368 mm 14-1/2" Mechanical Specifications for LS Plus 200 [ Dimensions are for Reference Only ] Mounting: External mounting brackets with 0.41"...
Note: Remote Alarm Remote Alarm Remote Alarm Contacts Contacts Contacts Wire Range Change State with Loss NC Contact Closed NO Contact Open #24 to #14 AWG of Power with SPD powered with Power OFF and Functional or SPD Requires 3X Torque [ Normal State ] Replacement Remote Alarm...
Page 10
218 mm 8-5/8" 178 mm 7-1/16" 508 mm 586 mm 20" 23-1/16" 152 mm 406 mm 6" 16" Use 3/8" [ 10 mm ] Mounting Hardware 548 mm 21-9/16" 368 mm 14-1/2" Mechanical Specifications for LS Plus 200 with Disconnect Switch [ Dimensions are for Reference Only ] Mounting: External mounting brackets with 0.41"...
Page 11
Remote Alarm Remote Alarm Note: Contacts Contacts Remote Alarm Contacts Change State with Loss Wire Range of Power Replacement Remote Alarm Contacts Normally Open Common NC C NO NC C NO 3X Wire Strip Lengths Normally Closed for Phase Connections Contact is Closed into the Disconnect when SPD is...
Page 12
Lock Out of Enclosure in the OFF Position if Required Pull Out Locking Tab to Install Install Lock Step 1 Turn Handle to the OFF Disconnect Handle must Position be in the OFF Position to Open or Close the Enclosure Door 3/16"-5/16"...