The Form C relay contact output connections are made to the spring clamp terminal
blocks. See Section 9.5. The chassis ground connection is made to the 1/4-20 studs.
See Section 9.6. This safety ground connection should be made before operating
the panel.
11.3
Checking Connections. Carefully check the polarity of input connections to the
distribution panel and output connections to the load before operating the panel.
Reverse connections will not harm the distribution panel which is POLARITY
NEUTRAL but may cause serious harm to the load. Check to make sure that the
chassis safety ground connection is made. Make sure that all connections are clean
and secure to minimize contact resistance.
11.4
Rear Safety Cover. Once all of the above have been completed, fit the clear plastic
safety cover to the back of the unit using the supplied mounting studs and screws.
Instruction for fitting the mounting studs the panel are included in the accessory kit.