Figure 9. Chassis Ground Connection - Infinite Transtector DCPDU2B Series Installation Manual

Table of Contents

Advertisement

Installation Manual
| DCPDU2B Series Power Distribution Units
9.6
12
Chassis Ground Connection. This is located on the left side of the chassis as shown
in figure 9 below and is a pair of 1/4-20 bolts.
(1/4-20 THREAD)
The recommended cable size for this connection is 2/0 AWG terminated with a Panduit
LCDN2/0-14A-X or equivalent lug. Torque bolts to 62 in-lbs.
NOTE THAT IT IS ESSENTIAL THAT THIS TERMINAL IS CONNECTED TO THE
SYSTEM FRAME GROUND TO ENSURE SAFE OPERATION.