Siemens RDF870KN Series Manual page 31

Touch screen flush-mounted pm2.5 & iaq controllers with knx or rs485 modbus
Hide thumbs Also See for RDF870KN Series:
Table of Contents

Advertisement

Object
59
PM2.5 setpoint
60
CO
setpoint
2
61
Local DO1
62
Local DO2
63
Local DO3
64
Local DO4
65
Room temperature source
66
Current working mode
67
Model name
68
Model type
69
Room temperature present value
70
Outdoor temperature present value
71
PM2.5 present value
72
CO
present value
2
73
VOC present value
74
Humidity present value
75
Alarm present value
76
Room temperature
77
Outdoor temperature
78
8)
PM2.5_External
79
8)
CO2_External
8)
80
VOC_External
81
8)
Humidity_External
82
8)
Alarm_External
83
Dummy_DI_X1
Siemens
Smart Infrastructure
Read
Write
40101 1
RW
0x03
0x06
40102 1
RW
0x03
0x06
40103 1
RW
0x03
0x06
40104 1
RW
0x03
0x06
40105 1
RW
0x03
0x06
40106 1
RW
0x03
0x06
40107 1
RW
0x03
0x06
40108 1
RW
0x03
0x06
30002 1
RO
0x04
30003 1
RO
0x04
30004 1
RO
0x04
30005 1
RO
0x04
30006 1
RO
0x04
30007 1
RO
0x04
30008 1
RO
0x04
30009 1
RO
0x04
30010 1
RO
0x04
30011 1
RO
0x04
30012 1
RO
0x04
30013 1
RO
0x04
30014 1
RO
0x04
30015 1
RO
0x04
30016 1
RO
0x04
30017 1
RO
0x04
30018 1
RO
0x04
2
60
SPML...SPMH
2
1000
SPCL...SPCH
2
0
0: Off:
1: On
0: Off:
2
0
1: On
2
0
0: Off:
1: On
0: Off:
2
0
1: On
2
1
0: Built in temperature;
1: Remote
2
1
0: OFF;
1: ON;
2: ECO;
3: Protection (Room unit only)
4
-
0: Modbus model; 1: KNX model
4
-
0: Room controller; 1: Room unit
4
-
4
-
4
-
4
-
4
-
4
-
4
-
0: No alarm;
1: Have alarm
4
x100
0
0...50 ° C
4
x100
0
-50...200 ° C
4
0
0...1000
4
0
0...2000
4
0
0...10 mg/m
0...100 %
4
0
0...100 %
4
-
0: OPEN;
1: CLOSE;
2: Invalid
4
-
0: OPEN;
1: CLOSE;
3
;
31
A6V11439454_en--_d
2021-03-31